Campbell Hausfeld SDM-CVO4 Manual Do Utilizador

Página de 30
SDM-CVO4 4-Channel Current/Voltage 
Output Module 
The SDM-CVO4 is a synchronously addressed datalogger peripheral designed to allow the 
datalogger to output variable voltage or current signals under program control.  
 
Figure 1.  SDM-CVO4 (shown without mounting brackets) 
1.  Introduction 
The SDM-CVO4 expands the analogue output capability of Campbell Scientific 
dataloggers. Each output can be set to 0-10V or 0-20mA by the datalogger. The 
output can be scaled and limited to 4-20mA by the datalogger program if required 
by the application. 
Typical applications will include driving remote ‘current-loop’ display units, re-
transmitting measured values to industrial control systems which have current or 
high voltage inputs, sending control signals to valve controllers and providing 
excitation voltages or currents to external sensors.  
Each output is isolated both from the datalogger and the other channels on the 
CVO4, thereby avoiding ground loop problems that might otherwise occur. 
In the current mode the output can either act as a 2-wire current controller, where 
the loop is powered from a remote voltage source, or it can be used to generate a 
0-20 mA current source using a voltage output derived from its own power 
supply.