Campbell Hausfeld SDM-CAN Manual Do Utilizador

Página de 74
SDM-CAN CAN-Bus Interface User Guide 
Once the buffer is complete, after using other P118s with this range of data types 
to construct the desired data frame, it is sent out onto the CAN-Bus by a further 
call of P118 with parameter 08 set to 25 or 26 (see below).  
Parameter 
Value 
Data Type 
Unsigned integer, most significant byte 1st.  
Unsigned integer, least significant byte 1st.  
Signed integer, most significant byte 1st.  
10 
Signed integer, least significant byte 1st.  
11 
4 byte IEEE floating point number, most significant byte 1st. 
12 
4 byte IEEE floating point number, least significant byte 1st.  
Setting parameter 08 in the range of  13..18 has the same function as in the7..12 
range, except that the data values written are logically ‘OR’ed with values 
previously written into the memory buffer. This allows complex bit patterns to be 
defined, sometimes changing only as little as one bit at a time.  
Parameter 
Value 
Data type 
13 
Unsigned integer, most significant byte 1st.  
14 
Unsigned integer, least significant byte 1st.  
15 
Signed integer, most significant byte 1st.  
16 
Signed integer, least significant byte 1st.  
17 
4 byte IEEE floating point number, most significant byte 1st. 
18 
4 byte IEEE floating point number, least significant byte 1st.  
 
Transmit individual data values onto the CAN-Bus: 
This range of parameter values instructs the datalogger to send a data value to the 
SDM-CAN in the format specified; it is loaded into the specified point in a data 
frame and then immediately transmitted onto the CAN-Bus. Bits within the data 
frame that are not set are left at zero. The data frame length is set to the minimum 
size (in whole bytes) required to hold the type of data value specified. 
Parameter Value 
Data Type 
19 
Unsigned integer, most significant byte 1st.  
20 
Unsigned integer, least significant byte 1st.  
21 
Signed integer, most significant byte 1st.  
22 
Signed integer, least significant byte 1st.  
23 
4 byte IEEE floating point number, most significant 
byte 1st. 
24 
4 byte IEEE floating point number, least significant 
byte 1st.  
 