2.2. Wiring 
When conducting wiring, follow the instructions below. 
•  Use shield wire for control signal line and ground the unit with shield wire 
    (Use twisted pair shield cable for wiring of the analog monitor output.) 
•  Never bind the signal line and main circuit connection wire together. 
•  Fix the communication cables after connected. 
 
Terminal Block 
Applicable wire size 
The wire length of 
peel off the end 
Using screwdriver 
(The blade tip) 
Tightening  
torque 
TB1 
0.2 to 2.5 mm
2
 About 
7mm 
0.6mm thickness 
and 3.5mm width. 
0.5 to 0.6 N
TB2 to TB4 
0.2 to 1.5mm
2
 About 
5mm 
0.4mm thickness 
and 2.5mm width. 
0.22 to 0.25 N
 
 
< Input/output terminal interface > 
 
Terminal 
symbol 
Function Electrical 
specification Internal 
circuit 
R2A 
R2B 
R2C
 
Relay contact 
point output 
Configuration of 1C contact point 
250Vac - 2A (cosφ=1) 
250Vac - 1A (cosφ=0.4) 
30Vdc - 1A   
R2A
R2B
R2C
Ry
 
LI5 
LI6 
LI7 
LI8 
Contact point 
input Changeover 
of sink or source 
No voltage contact input 
  24Vdc - 5mA 
Sink input(common voltage 24V) 
 ON  :less than 10Vdc 
 OFF :16Vdc or more 
Source input 
ON  :11Vdc or more 
OFF  :less than 5Vdc 
Note: 
Even when an external power supply 
is used (in sink logic mode i.e. when 
SINK(PLC) is selected), connect the 
reference potential-side (0V side) 
cable from the power supply to the CC 
terminal. 
 
 
 
 
 
24V power supply 
24Vdc power output (when SW is   
in any position other than PLC) 
24V internal output terminal   
    24Vdc - 60mA max 
PLC/ 
P24 
Common terminal 
for external 
power supply 
If SW is turned to the PLC position, 
this terminal can be used as a 
common terminal when an external 
power supply is used. 
SINK Logic(SW =SINK(INT))
SW
2.2k ohm
2.2k ohm
CC
LI5
LI6
LI7
LI8
SOURCE
P24/
PLC
SINK(PLC)
SINK
(INT)
P24
 
 
SINK Logic (SW =SINK(PLC))
SW
2.2k ohm
2.2k ohm
CC
LI5
LI6
LI7
LI8
SOURCE
P24/
PLC
SINK(PLC)
SINK
(INT)
P24
 
 
SOURCE Logic (SW =SOURCE)
SW
SOURCE
2.2k ohm
P24/
PLC
2.2k ohm
CC
LI5
LI6
LI7
LI8
SINK(PLC)
SINK
(INT)
P24
 
 
 
Lan current signal. 
Chose low current contacts to 
avoid poor attaching.