H9 ASD Installation and Operation Manual
OC
Over Current
ASD output current greater than 
 setting.
• Defective IGBT (UV, or W).
• ASD output to the motor is connected incorrectly. 
Disconnect the motor and retry.
• ASD output phase-to-phase short.
• The ASD is starting into a spinning motor.
• Motor/machine jammed.
• Mechanical brake engaged while the ASD is starting or 
while running.
• Accel/Decel time is too short.
• Voltage Boost setting is too high.
• Load fluctuations.
• ASD operating at an elevated temperature.
*OH
Overheat
ASD ambient temperature 
excessive.
• ASD is operating at an elevated temperature.
• ASD is too close to heat-generating equipment.
• Cooling fan vent is obstructed (see 
).
• Cooling fan is inoperative.
• Internal thermistor is disconnected.
OJ
Timer
Run-time counter exceeded.
• Type Reset required; select Clear run timer.
*OLI
ASD Overload
Load requirement in excess of 
the capability of the ASD.
• The carrier frequency is too high.
• An excessive load.
• Acceleration time is too short.
• DC damping rate is set too high.
• The motor is starting into a spinning load after a 
momentary power failure.
• The ASD is improperly matched to the application.
OLM
Motor Overload
Load requirement in excess of 
the capability of the motor.
• V/f parameter improperly set.
• Motor is locked.
• Continuous operation at low speed.
• The load is in excess of what the motor can deliver.
*OLR
Resistor 
Overload
Excessive current at the 
Dynamic Braking Resistor.
• Deceleration time is too short.
• DBR configuration improperly set.
LED 
Display
LCD 
Display
Description
Possible Causes