8315 L&J Tankway Software Description
TankGate Interface
38 
Installation and Operations Manual
4.9
Emulator (EMU)
The Emulator point allows the TankGate to emulate a Whessoe-Varec Model 
6820 Tank Scanning Unit (TSU). This point provides access for level, 
temperature data, and gauge status information from any type of tank gauge 
interface supported by the TankGate.
4.9.1
Parameters
The database parameters used by the EMU point are listed and described below:
Configuration Parameters
Function
Tag
The point description can contain 30 bytes of data and can 
include any printable ASCII character.  Descriptions can be used 
as information relevant to any aspect of the point, such as its 
use, location, operating information, etc.  The default 
description is set to “EMU.00”.
LevelUnits
Specifies the engineering units for the level data. 
F: feet, m: Millimeters
M: Meters
I: Inches
P: ft-in-16ths
The LevelUnits need to match the units specified during the 
gauge setup. 
TempUnits
Specifies the engineering units for the temperature data. 
TempUnitsSpecifies the engineering units for the temperature 
data. 
F: Fahrenheit
C: Celsius
The TempUnits needs to match the units specified during the 
gauge setup. 
DensityUnits
Specifies the engineering units for the density data. 
DensityUnitsSpecifies the engineering units for the density data. 
K: kg/m3
A: API
L=lbs/cu ft
The DensityUnits needs to match the units specified during the 
gauge setup.
PntRef1 - 50
Input point reference for the EMU point to monitor.  The PntRef 
parameter is set to the Level parameter for the tank gauge point.  
The temperature will be read at the same time as the level.  The 
EMU point interfaces tank gauge interface points:
WV1900 - Whessoe-Varec Model 1900