Omron CS1W-RPT01 Manual Do Utilizador
109
What Are Data Links?
Section 5-1
• There are three types of 1:N allocations.
• Programming Devices (including Programming Consoles) are used to set
the automatic data link mode in the DM Parameter Area of the PLC used
as the startup node.
as the startup node.
• Node 1 is the master node.
• Areas 1 and 2 can be selected from bit-access areas or the DM Area.
• The send area sizes of the master and slave nodes are the same for each
area.
• Send nodes are in the same ascending order as node numbers.
• All nodes can be specified to either participate or not participate in the
data link.
• The data link areas (data link start words) are common to all nodes partic-
ipating in the data links.
Note
1.
Automatic data link creation with 1:N allocations can only be used with the
following Controller Link Units and Support Boards:
following Controller Link Units and Support Boards:
2.
Controller Link Units and Support Boards other than those listed above
cannot participate in 1:N allocation data links. They can, however, join the
network if a parameter in the DM Parameter Area is set so that they do not
participate in the data links.
cannot participate in 1:N allocation data links. They can, however, join the
network if a parameter in the DM Parameter Area is set so that they do not
participate in the data links.
3.
The Controller Link Support Board (3G8F7-CLK21-V1) can be used in au-
tomatic data link creation with 1:N allocations, but it cannot be the startup
node. Use a Controller Link Unit (CS1W-CLK21-V1 or CJ1W-CLK21-V1)
on the same network as the startup node.
tomatic data link creation with 1:N allocations, but it cannot be the startup
node. Use a Controller Link Unit (CS1W-CLK21-V1 or CJ1W-CLK21-V1)
on the same network as the startup node.
4.
For automatic data link creation with 1:N allocations, use the CX-Net in CX-
Programmer version 3.2 or higher.
Programmer version 3.2 or higher.
1
4
2
3
1
2
1
3
1
4
1
4
2
3
1
2
1
3
1
4
Node 1
Node 2
Node 3
Node 4
Area 1
Area 2
Type
Model
Wired networks
CS1W-CLK21-V1 (for CS Series)
CJ1W-CLK21-V1 (for CJ Series)
3G8F7-CLK21-V1 (for PCI bus)
CJ1W-CLK21-V1 (for CJ Series)
3G8F7-CLK21-V1 (for PCI bus)