Liebert OC-485 Folheto

Página de 2
Liebert IntelliSlot
®
 OC-485 Card
Quick Start Guide
I
NSTALL
• Locate the Intellislot option bay for your Liebert equipment. You might 
need to remove a plastic cover.
• Insert the Liebert IntelliSlot OC-485 Card into the Intellislot bay.
• Secure the card with the supplied screws.
• Connect RS-485 cable.
IGM: The card ships with IGM service enabled. (No configuration is 
required for IGM communications.)
Modbus: To assign a server ID address, use the Service Terminal to con-
figure the card. Proceed to Steps 2 & 3.
C
ONNECT
 
THE
 C
ABLE
• Locate the blue serial configuration cable (null modem) that shipped 
with the card.
• Connect the configuration cable to the DB-9 port on the card and to a 
COM port on your PC.
C
ONFIGURE
 
THE
 C
ARD
• Use terminal emulation soft-
ware, such as HyperTerminal™, 
to open a direct connection to 
the card.
• Press ENTER for the Main 
Menu, above right.
• Select option 1 and press Enter 
to access the communications 
settings, shown at right.
• Enter 1 and press enter to 
enable the Modbus application.
• At the next screen, enter 3 to 
access the screen to set the 
server ID for the Liebert 
IntelliSlot OC-485 Card (the ID 
default is 1, but may be any 
number up to 255). In the 
example at right, the server ID 
is “2.”
• Press Esc to return to the main 
Menu.
• Enter X and press Enter to exit 
HyperTerminal, save your 
changes and reboot the card.
Baud Rate:
9600
Data Bits:
8
Parity:
None
Stop Bits:
1
Flow Control:
None
NOTE
When installing the card in a Liebert NX
, configure the 
communication port of the Liebert NX to 2400 baud.  Refer to the 
Liebert NX user manual for instructions.