Operating Conditions
2
2.0
O
PERATING
 C
ONDITIONS
2.1
Proper Application
The XDK is a water-cooled enclosure and is intended for removing heat from electronic equipment 
inside the cabinet. The cooling system in the cabinet is thermally independent of the room air. Water 
is used to cool equipment installed in the XDK. No additional cooling of the server room is required.
NOTE
Under certain conditions, a small amount of heat, (approximately 0.5kW), can escape into the 
room.
!
CAUTION
Risk of improper operation. Can cause equipment damage. For reliable function of the XDK, 
cold water  must be available in the correct amount, and at the correct  temperature and 
pressure. Observe water quality specified in VGB-R 455 P. (see 8.0 - Water Purity 
Table 1
General operating data
Ambient temperature
50°F to 95°F (10°C to 35°C)
(other temperatures upon request)
Absolute humidity in the installation location
8g H
2
O/ kg air maximum
Water temperature, supply
54°F (12°C); other temperatures upon request
Water temperature, return
64°F (18°C); other temperatures upon request
Water connection
from below
Condensed water connection
from below 
Nominal voltage
200V to 264V (50Hz and 60 Hz)
Maximum operating pressure
145 PSI (10 bar)