CANopen Communication Module DVPCOPM-SL
 
DVP-PLC Application Manual 
3
1 Introduction 
1.  To ensure correct installation and operation of DVPCOPM-SL, please read this chapter carefully before 
using your DVPCOPM-SL. 
2.  This chapter only provides introductory information on DVPCOPM-SL. For more detailed information on 
CANopen protocol, please refer to relevant references or literatures. 
3.  DVPCOPM-SL is a CANopen module operating on the left side of DVP-SV series PLC MPU. When DVP-SV 
is connected to CANopen network through DVPCOPM-SL, DVPCOPM-SL will serve as the data exchange 
interface between DVP-SV and other slaves on the bus. DVPCOPM-SL is in charge of sending the data in 
DVP-SV to the slaves on the bus, and at the same time collecting the data returned from each slave and 
sending them back to DVP-SV. 
1.1 Features 
DVPCOPM-SL can be used as the master in CANopen network, as well as the slave for other masters. 
As a master, DVPCOPM-SL features: 
z  Complying with CANopen standard protocol DS301v4.02. 
z  Supporting NMT Master Service. 
z  Error control: Supporting Heartbeat/Node Guarding Protocol. 
z  Supporting PDO Service. 
Max. 200 RxPDOs and 390 bytes of data 
Max. 200 TxPDOs and 390 bytes of data 
Each slave can be allocated maximum 8 TxPDOs and 8 RxPDOs. 
z  PDO transmission type: Supporting event trigger, time trigger, synchronous cycle, and synchronous 
non-cycle. 
z  PDO mapping: Every PDO is able to map maximum 32 parameters. 
Type of mapping data supported: 
Storage space 
Data type 
1 bit 
BOOL 
8 bits 
SINT USINT BYTE 
16 bits 
INT UINT WORD 
32 bits 
DINT UDINT REAL DWORD 
64 bits 
LINT ULINT LREAL LWORD 
z  Supporting SDO Service. 
Number of server: 0 
Number of user: 3 
z  Supporting standard expedited SDO transmission mode. 
z  Supporting Auto SDO function. Able to execute maximum 20 Auto SDOs to each slave. 
z  Supporting reading/writing of data in slave by using SDO Service in the ladder diagram in PLC. 
z  Supporting Emergency Protocol: 
Able to store 5 latest Emergency messages for each slave. 
Able to indicate Emergency messages in slave from digital display. 
Able to read Emergency message through the ladder diagram in PLC. 
z  SYNC producer; Range: 0 ~ 65,535ms.