Delta Electronics VFD-S Manual Do Utilizador

Página de 185
Chapter 2 Installation and Wiring|VFD-S Series 
Revision August 2008, SE09, SW V2.61 
2-17
2.4.1 Basic Wiring  
„ 
Make sure that power is only applied to the R/L1, S/L2, T/L3 terminals. Failure to comply 
may result in damage to the equipment. The voltage and current should lie within the 
range as indicated on the nameplate. 
„ 
Check the following items after completing the wiring: 
1. 
Are all connections correct? 
2. 
No loose wires? 
3. 
No short-circuits between terminals or to ground?
 
 
A charge may still remain in the DC bus capacitors with hazardous voltages even if the power 
has been turned off. To prevent personal injury, please ensure that the power is turned off and 
wait ten minutes for the capacitors to discharge to safe voltage levels before opening the AC 
motor drive. 
 
DANGER!
 
1. 
All the units must be grounded directly to a common ground terminal to prevent electric shock, 
fire and interference. 
2. 
Only qualified personnel familiar with AC motor drives are allowed to perform installation, wiring 
and commissioning. 
3. 
Make sure that the power is off before doing any wiring to prevent electric shocks. 
 
 
Basic Wiring Diagrams 
 
Users must connect wires according to the circuit diagrams on the following pages. Do not plug a 
modem or telephone line to the RS-485 communication port or permanent damage may result. Pins 
1 & 2 are the power supply for the optional copy keypad only and should not be used for RS-485 
communication.