Delta Electronics VFD-S Manual Do Utilizador

Página de 185
Chapter 5 Parameters|VFD-S Series 
Revision August 2008, SE09, SW V2.61 
5-27
 
Group 2: Operation Method Parameters 
2-00 
Source of Master Frequency Command 
 
 
 
Factory Setting: d0
 
Settings 
d0 
Master Frequency input determined by digital keypad. (record the 
frequency of power loss and it can do analog overlap plus) 
 
 
d1 
Master Frequency determined by analog signal DC 0V-10V 
(external terminal AVI). (won’t record the frequency of power loss 
and it can’t do analog overlap plus) 
 
 
d2 
Master Frequency determined by analog signal DC 4mA-20mA 
(external terminal AVI). (won’t record the frequency of power loss 
and it can’t do analog overlap plus) 
 
 
d3 
Master Frequency determined by Potentiometer on the digital 
keypad. (won’t record the frequency of power loss and it can do 
analog overlap plus) 
 
 
d4 
Master Frequency operated by RS-485 serial communication 
interface and record frequency of power loss. (record the frequency 
of power loss and it can do analog overlap plus)  
 
 
d5 
Master Frequency operated by RS-485 serial communication 
interface and won’t record frequency before power loss. (won’t 
record the frequency of power loss and it can do analog overlap 
plus) 
 
This parameter sets the Frequency Command Source of the AC drive. 
 
If the Frequency Command Source is external (DC 0 to +10V or 4 to 20mA), please make 
sure the (AVI) terminal jumper is in the proper position as shown below. 
 
Position of jumper: Please open the top cover. It is at the lower-left corner of the panel. The 
jumper J1 determines the type of external analog input, either DC voltage signal or current 
signal. 
J1
Voltage signal input(0-10V)
Current signal input(4-20mA)
 
 
When setting analog overlap plus, it needs to set Pr. 2-06 to select AVI or ACI.