LST ISM1-3 Folheto

Página de 1
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
ISM1-3_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
Specifi cations
Operating voltage 
Supply through loop voltage
Current consumption 
max. 0.2mA
Ambient temperature 
-5°C to +50°C
Dimensions L × W × H 
70 × 24 × 15 (mm)
Weight 
20g
Approval 
VdS G296012
Order number 
249029
Order name 
Isolator Module/Anal./Apo ISM1-3
The Isolator Module ISM1-3 is used on the ADM loop with 
Apollo/Discovery protocol and disconnects the loop in 
the event of a short circuit of the loop connection. 
Thereby only the loop elements located between two 
isolator modules are affected by the short circuit.
The Fire Detection Control Panels Series BC216 report 
the affected loop elements as faulty and operate the 
remaining loop sections, which are not faulty, from both 
ends of the loop, until the fault is removed.
•   Safe disconnection of a faulty loop 
section
•  For use in an Apollo/Discovery loop
•   Installation in commercial installation 
boxes or in the LST standard grid
•  Small design