Description
With the Zone Extension Board ZEB2-1 a Fire Detection 
Control Panel BC06-1 or BC06-2 can be extended from 
four to six detector zones. In the event of an alarm, the 
fi re detection control panel indicates the activation of 
the detector zone via LED. Depending on the detector 
type, each of the two detector lines can be individually 
parameterised as detector zone for fi re alarms or as 
detector zone for fault messages.
Alarms from manual call points and from automatic de-
tectors that are connected together to a detector line 
can be differentiated and thus evaluated differently by 
the fi re detection control panel, by means of an optional 
coding module.
Each  input  of  the  zone  extension  board  is  protected 
against overvoltage and thus provides high system sta-
bility.
•   Extends Fire Detection Control Panels 
BC06-1 and BC06-2 by further 2
conventional detector zones
•   Individual setting of detector zone 
function
•   Differentiation between the activation 
of automatic detectors and manual 
call points on the same detector line
•   Lines monitored for wire breakage, 
short circuit, and short to earth
Specifi cations
Current consumption at 24V 
typ. 14mA (line termination 5.6kΩ, without detectors)
 
typ. 7mA (line termination 47µF, without detectors)
Line voltage 
typ. 20V (line termination 5.6kΩ)
 
typ. 23V (line termination 47µF)
Line current 
typ. 3.7mA (line termination 5.6kΩ)
 
typ. 0mA (line termination 47µF)
Line termination 
5.6kΩ or 47µF
Line resistance 
max. 50Ω per core
Ambient temperature 
-5°C to +50°C
Dimensions L × W × H 
103 × 58 × 15 (mm)
Weight 
34g
Order number 
210210
Order name 
Zone Extension Board ZEB2-1