A
Building Safety. Building Security.
Description
The Loop Interface LIF64-1 allows for the connection of 
one ADM loop with bi-directional data exchange and up 
to 128 detector zones to fi re detection control panels 
Series BC216. The ADM loop supports 198 elements 
(99  detectors  and  99  modules)  with  System  Sen-
sor/200 protocol or 126 elements (detectors and/or 
modules) with Apollo/Discovery protocol.
Each ADM loop can be subdivided into a maximum of 
128 detector zones. The function of the detector zone 
(automatic fi re detector zone, technical message, fault 
detection zone, etc.) as well as the element type (e.g., 
automatic detector, manual call point, monitor module, 
control  module  or  conventional  zone  module)  can  be 
parameterised on the fi re detection control panel.
A two-sided isolator is integrated on the Loop Interface 
(at  the  beginning  and  the  end  of  the  loop).  The  loop 
wiring can be realized as ring, branch or any given com-
bination of sectional rings and branches.
Thanks to the ring-shaped cabling, all elements on the 
loop remain functional in the event of a single wire brea-
kage. In addition, the wire breakage is displayed on the 
control panel. What is more, the operational reliability of 
those parts of the loop that are not affected is secured 
in the event of a short circuit. Unshielded wires can be 
used for the fi re detector cabling and, therefore, exis-
ting installations can be assumed smoothly and existing 
cabling can be reused.
On the control panel, you can perform a maintenance 
prognosis  for  each  connected  smoke  detector.  The 
continuous monitoring of the detector function allows 
for cost-optimized operation and optimum planning of 
the maintenance works.
The Loop Interface provides a processor of its own. At 
a possible central processing board failure, the diver-
sifi ed redundancy concept thus ensures reliable alarm 
recognition.
•   Intelligent analogue ringbus 
technology
•   Up to 99 detectors and 99 modules 
with System Sensor/200 protocol
•   Up to 126 detectors or modules with 
Apollo/Discovery protocol
•   Easy setup of loop elements thanks 
to AUTO confi guration
•   Maintenance prognosis for smoke 
detectors