LST LAM48-1 Manual Do Utilizador

Página de 3
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
PTU288-1_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
The Remote Tableau Drive Unit PTU288-1 allows to op-
tically signal events of a Fire Detection Control Panel 
Series BC216 or BC016, or of an Extinguishing Control 
Panel  Series  LC216,  on  an  optional  synoptic  remote 
tableau. In addition, a built-in buzzer signals the alarm 
or fault condition of the control panel. 
Up to 3 LED Display Fields LAB48 or LED Connection 
Modules LAM48-1 can be connected to the remote tab-
leau drive unit in any combination.
In accordance to the parameterisation, the LEDs can be 
used to display the conditions of detectors, detector zo-
nes, actuations, actuation elements, alarming devices, 
transmitting devices, extinguishing systems or fl ooding 
zones as well as the most important system conditions 
of the fi re detection control panel (e.g., summary alarm, 
fault condition or disablement condition). If needed, it is 
also possible to combine several events into a summary 
display.
Furthermore, the PTU288 has 5 freely parameterisable 
control inputs.
The remote tableau drive unit is connected to the fi re 
detection control panel via the INFO bus. Auxiliary mo-
dules are not needed for connection to Control Panels 
Series BC216. A Serial Interface Module SIM016-3 is 
necessary for connecting the PTU288 to a Fire Detec-
tion Control Panel Series BC016.
The PC software PARSOFT is used to parameterise the 
remote tableau drive unit via the USB interface.
The componentry is prepared for direct installation into 
the LED Display Tableau LAT288-1 or LAT288-1CE. The 
componentry can also be mounted in any housing in the 
LST standard grid, using the supplied mounting parts.
•   Optically and acoustically signals 
the events of a fi re detection or 
extinguishing control panel
•   Actuation of up to 144 LED pairs, 
single LEDs or relays
•   Single or summary indication 
parameterisable
•  Connection to the INFO bus
•   Easy parameterisation by means of 
PC software PARSOFT
Specifi cations
Operating voltage 
15 – 31VDC
Current consumption at 24V 
typ. 15mA (without LED modules)
Ambient temperature  
-20°C to +60°C
Dimensions L × W × H 
150 × 75 × 20 (mm)
Weight 
76g
Order number 
252012
Order name 
Remote Tableau Drive Unit PTU288-1