Powerware 1500 VA - 60kVa Manual Do Utilizador

Página de 120
EATON CORPORATION  Reference Guide & Price Book 
THREE-PHASE SERIES 9
Powerware BladeUPS (continued)
POWERWARE RACK POWER MODULE CONFIGURATOR
Description 
 
Quantity 
Part 
 
 
List
 
 
 
Number Digit 
Value 
 
Price 
Output Receptacle Plate #1 & 
L21-20R 
8 & 9 
 
$400 
 
Output Receptacle Plate #2 
L21-30R 
 
 
$445 
 
 
L6-15R 
 
 
$245 
 
 
L6-20R 
 
 
$260 
 
 
L6-30R 
 
 
$200 
 
 
5-15R 
 
 
$170 
 
 
5-20R 
 
 
$175 
 
 
L14-20R 
 
 
$180 
 
 
L14-30R 
 
 
$245 
 
 
IEC320-C13 (208v) 
12 
 
 
$180 
 
 
IEC320-C19 (208v) 
 
 
$160 
 
L15-20 
 
 
 
$400 
 
L15-30 
 
 
 
$445 
 
C13 (230v) 
 
 
 
$180 
 
C19 (230v) 
 
 
 
$160
Metering Choices 
Power Equalizer 
 
10 
 
$0 
 
 
Energy Management System, NO card 
 
 
Available May 2007 
$695 
 
 
Energy Management System, with card 
 
 
Available May 2007  
$1,025 
Meter Configuration 
 
 
11 
 
 
TVSS Option 
None 
 
12 
 
$0 
 
 
TVSS Installed (208v) 
 
 
 
$350 
 
TVSS Installed (400v) 
 
 
 
$350 
Future Option 
 
 
13 
 
 
 
 
 
 
14 
 
 
 
 
 
 
15 
 
 
Notes
How to order:
1. Select base model voltage (208V or 400V), 2. Select input connector option, 3. Select input cord length (corded units only), 4. Select first receptacle plate 
option, 5. Select second receptacle plate option, 6. Select metering option, 7. Select TVSS option
Example of configured model part number: Y03111022300000
SERVICE PLANS 
 
 
 
 
 
For service plans, please see the service section beginning on page 81.  
 
POWERWARE BLADEUPS BATTERY BACKUP TIMES (IN MINUTES)
Load 
 
Internal  
 
 
 
 
(kw) 
Load % 
Battery 
+(1) EBM 64 
+(2) EBM 64 
+(3) EBM 64 
+(4) EBM 64
1.6 
13% 
55 
118 
183 
253 
329
2.4 
20% 
37 
78 
119 
163 
211
33% 
23 
46 
69 
94 
120
50% 
13 
30 
44 
59 
76
67% 
21 
32 
43 
54
9.6 
80% 
6.9 
17 
26 
34 
44
12 
100% 
4.8 
12 
20 
27 
34
Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
1 EBM needed per BladeUPS.
POWERWARE BLADEUPS BATTERY BACKUP TIMES (Parallel UPS, in minutes) 
Number of 
Total Load 
 
Internal  
 
 
 
 
UPS Models 
(kw) 
Configuration 
Battery 
+(1) EBM 64 
+(2) EBM 64 
+(3) EBM 64 
+(4) EBM 64
60 
N+1 
15 
22 
29 
37
48 
N+1 
6.9 
17 
26 
34 
44
36 
N+1 
7.7 
18 
28 
37 
47 
24 
N+1 
21 
32 
43 
54
12 
N+1 
13 
30 
44 
59 
76