Multi-Tech Systems 7600 Manual Do Utilizador

Página de 372
ION 7500 / ION 7600 User’s Guide
Power Frequency
Power Quality: ION Meters and EN50160 Technical Note
Page 303
Power Frequency Default Measurements
* This data is recorded once a week by Data Recorder module 17.
Optionally, the data below can be recorded every 10 minutes by Data Recorder 32.
Register Label
Source Module Type
Description
Freq N*
Signal Limit Evaluation
number of valid intervals (voltage on all phases within +/- 15% of nominal)
Freq N invld*
number of invalid intervals 
Freq N1*
number of valid intervals in which the freq deviates from the nominal by more than +/-1%
Freq N2*
num of valid intervals in which the freq deviates from the nominal by more than +4% or -6% 
PO Freq N
Store
Freq N of the previous Observation Period
PO Freq N1
Freq N1 of the previous Observation Period
PO Freq N2
Freq N2 of the previous Observation Period
Freq mean-ep
Sliding Window Demand
average Frequency over 10s (used for display purposes)
Freq mn-op
Minimum
minimum mean Frequency (Freq mean-ep) over 1week (used for display purposes)
Freq mx-op
Maximum
maximum mean Frequency (Freq mean-ep) over 1week (used for display purpose)
Freq N1/N
Arithmetic
N1/N ratio
Freq N2/N
N2/N ratio
PO Freq N1/N
N1/N ratio of the previous Observation Period
PO Freq N2/N
N2/N ratio of the previous Observation Period
Register Label
Description
PQ Freq mean
average Frequency over 10minutes
PQ Freq low
minimum Frequency over 10 minutes (HS measurement)
PQ Freq high