SECTION 7: OPTIONAL HEATER ACCESSORIES
7.1 U-Tube Configuration
Heaters (except CTH2-40) are approved for optional 
U-Tube configurations. 
The U-Tube may be installed in either a standard hor-
izontal position, a 45° position or in an opposite 45° 
position as show
9. When using a U-Tube configuration, the following 
additional rules must be adhered to:
• A minimum of 10' (3 m) on CTH2-60/80 and a min-
imum of 15' (4.5 m) on CTH2-100/125/150/175 is 
required between the burner and the U-Tube.
• The correct turbulator (
must be installed in the last standard section of 
tube.
• The burner must never be operated in a tilted posi-
tion.
• The heater must be properly supported at all loca-
tions
WARNING
Cut/Pinch Hazard
Wear protective gear during installation, 
operation and service.
Edges are sharp.
Failure to follow these instructions can result 
in injury.