Chapter 3 
 
 
 
 
Page 9 of 16 
Chapter 3 – Configuring the Inverter 
 
The configuration of inverter parameters will depend on the specific functionality and performance required for 
your application. The basic functionality of the board is designed to interface with a two pushbutton, 
two-position (two-speed) momentary contact type pendant commonly used for crane and hoist applications. This 
is the basis for the descriptions of the functions of the board presented in this manual. The setup in the table 
below will result in infinitely variable speed between the programmed MIN and MAX speeds. The defined 
functions of the pushbuttons are as follows: 
 
UP 
DOWN 
 
UP, first detent: UP – accelerate to minimum speed 
UP, second detent: UP – increase speed while held, up to MAX speed (or go to second speed, see page 10)
 
 
 
DOWN, first detent: DOWN – accelerate to minimum speed (RESET fault when inverter is 
                                  STOPPED and in a fault state) 
DOWN, second detent: DOWN – increase speed, up to MAX speed (or go to second speed, see page 10) 
 
Pushing either the UP or DOWN pushbutton to the first position causes the inverter to go to the minimum 
configured speed in that direction. Pushing that button further to its second position will cause speed to increase 
in that direction. Releasing back to first position will hold that last speed. Releasing the pushbutton all the way 
will cause the inverter to come to a stop. If that button is re-pressed to the first position before stop is reached, 
that speed will be maintained. 
 
In order to achieve this basic functionality, certain parameters must be set differently from factory default 
values, as described in the following table. 
 
Parameter 
Code 
Function Setting 
Comment 
F002 
Acceleration Time 
Note 1 
Set a value between 1 and 3600 seconds, depending on application 
F003 
Deceleration 
Time 
Note 1 
Set a value between 1 and 3600 seconds, depending on application 
A001 
Frequency 
Command 
02 
Tells the inverter to read speed reference from internal register 
A002 
Run Command 
01 
Tells the inverter to take the RUN command from the control terminals 
A004 
Maximum 
Frequency 
Note 1 
Depending on the motor limits and application requirements, set the 
appropriate value 
A061 
Upper Frequency 
Limit 
Note 1 
Usually the same value as A004 
A062 
Lower Frequency 
Limit 
Note 1 
Lowest speed for continuous operation (MIN speed), usually 6 to 10 Hz or 
so. This is the speed that will be commanded at the first pushbutton position.
00 
For Non-Load Brake Hoist, or for traverse applications: 00 (factory default) 
Stop Mode 
Selection 
B091 
01 
For Load Brake Hoist applications: 01 (free-run or coast to stop) 
00 
SJ200 = [FW] Forward run 
no 
SJ700 Open Loop = [NO] No function 
Terminal 1 
Function 
C001 
56 
SJ700 Closed Loop = [MI1] 
01 
SJ200&SJ700 Open Loop = [RV] Reverse run 
Terminal 2 
Function 
C002 
57 
SJ700 Closed Loop = [MI2] 
Terminal 3 
Function 
C003 
27 
[UP] Accelerate speed input 
Terminal 4 
Function 
C004 
28 
[DN] Decelerate speed input