Bosch D6100 Manual Do Utilizador
Conettix D6600/D6100 | Computer Interface Manual | 3.0
Computer Communication Protocols
.
Bosch Security Systems, Inc. | 1/07 | 4998122703-01
25
3.1.25 Telim (Message Type n)
D6500 Byte Description
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
h n R R L s A A A A A A s E T T Z
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
Telim Example
Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z t Z
Table 30:
Telim (Message Type n) Byte Description
# Title
Description
1
Header Character
(
(
h
)
Optional. Check with the computer automation software for compatibility.
2 Message
Type
n
3-4
Receiver Number
Receiver gateway number from 01 to 99.
5 Line/Group
Number
Line number in the receiver gateway that sent the message.
6
Space
One space.
7-12
Account Number
Six digit account number.
13
Space
One space.
14 E
Event code.
15-32
TTZZZZZZZZZZZZ
Input line number.
33 Trailer
Character
Typically, HEX 14.
3.1.26 Text Message (Message Type 3)
D6500 Byte Description
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22
Type 3 Example
h 3 r r l P R I N T E R v v . v v t
Table 31:
Text Message (Message Type 3) Byte Description
# Title
Description
1
Header Character
(
(
h
)
Optional. Check with the computer automation software for compatibility.
2 Message
Type
3
3-4
Receiver Number
Receiver gateway number from 01 to 99.
5 Line
Number
Line number fixed at 1.
6-21
Message Text
Sixteen characters in length.
22 Trailer
Character
Typically, HEX 14.