Mitsubishi Electronics QSPCU Manual Do Utilizador

Página de 224
4
CPU MODULE
4.3 Switch Operation after Writing a Program
 
4
 - 5
1
O
VE
R
VI
EW
2
S
YST
EM
 
CONF
IGURA
T
ION
3
GENERA
SPE
CI
FI
CA
TI
O
N
4
CPU M
O
DUL
E
5
PO
W
E
R SUP
P
LY
 
M
O
DUL
6
B
ASE
 UNI
7
BA
TT
ER
Y
8
CPU M
O
DUL
E ST
ART
-
UP P
ROCEDURE
S
4.3  Switch Operation after Writing a Program
Programs can be written to the CPU module in either the STOP or RUN status.
(1) When writing a program with the CPU module set to "STOP"
(a) Set the RUN/STOP/RESET switch to STOP.
The "RUN" LED turns Off, and the module is placed in the STOP status.
Write a program from GX Developer to the CPU module in the STOP status.
(b) Reset with the RUN/STOP/RESET switch.
The CPU module is reset. (
(c) Set the RUN/STOP/RESET switch to RUN.
The "RUN" LED  turns on, and the CPU module is placed in the RUN status.
(2) When writing a program during RUN
When writing a program during RUN, the operation for the RUN/STOP/RESET switch 
is not required.
POINT
1. The program modified online during boot operation is written to the program 
memory.
      After making online program change, also write the program to the standard 
ROM of the boot source memory. If the program is not written in the standard 
ROM, the old program will be executed at the next boot operation.
      For details of the boot operation, refer to the manual below.
      
 QSCPU User's Manual (Function Explanation, Program Fundamentals)
2. To stop the CPU module, the remote operation of GX Developer can also be 
used.
      In this case, the operation for the RUN/STOP/RESET switch is not required.
      For details on the remote operation of GX Developer,  refer to the following 
manual.
      
GX Developer Version 8 Operating Manual