Emerson BACNET IP Manual Do Utilizador

Página de 372
Modbus 485 and Modbus IP Protocols - Thermal Management Products
83
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 27
Liebert Challenger 3000
, Liebert Deluxe System/3
, Liebert Himod
, Liebert ICS
- Input and Holding - LAM
Controller
Advanced Microprocessor - LAM
Liebert Products
Liebert Challenger 3000
Liebert Deluxe System/3
Liebert Himod (LNA version - Using Liebert SiteScan
®
)
Liebert ICS
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale 
Notes / Units
Status Points (View)
Temperature
40001
1
-
Humidity
40002
1
-
Cooling
40003
1
1=On / 0=Off
Heating
40004
1
1=On / 0=Off
Humidification
40005
1
1=On / 0=Off
De-humidification
40006
1
1=On / 0=Off
Econ-O-Cycle
40007
1
1=On / 0=Off
Stages
40008
1
-
% Capacity
40009
1
-
Unit Status (On / Off)
40018
1
1=On / 0=Off (R/W)
Analog input 1
40023
1
A/D raw value w/ slope=1 and offset = 0
Analog input 2
40024
1
A/D raw value w/ slope=1 and offset = 0
Analog input 3
40025
1
A/D raw value w/ slope=1 and offset = 0
Analog input 4
40026
1
A/D raw value w/ slope=1 and offset = 0
Alarm Points
Discrete alarm objects available;
use autodiscover for this unit
Communications
40289
1
Bit 0
Local Off
40289
1
Bit 1
Remote Off
40289
1
Bit 2
High Head Pressure 1
40289
1
Bit 3
High Head Pressure 2
40289
1
Bit 4
Loss of Airflow
40289
1
Bit 5
Standby Glycol Unit On
40289
1
Bit 6
Liquid Detected
40289
1
Bit 7
Change Filters
40289
1
Bit 8
High Temperature
40289
1
Bit 9
Low Temperature
40289
1
Bit 10
High Humidity
40290
1
Bit 0
Low Humidity
40290
1
Bit 1
Humidifier Problem
40290
1
Bit 2
No Water in Humidifier Pan
40290
1
Bit 3
Compressor 1 Overload
40290
1
Bit 4
Compressor 2 Overload
40290
1
Bit 5
Main Fan Overload
40290
1
Bit 6
Manual Override
40290
1
Bit 7
Smoke Detected
40290
1
Bit 8
Loss of Water
40290
1
Bit 9
Standby Unit On
40290
1
Bit 10
Low Suction
40291
1
Bit 0
Short Cycle
40291
1
Bit 1
Loss of Power
40291
1
Bit 2