Emerson MODBUS IP Manual Do Utilizador
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
148
Table 55
Liebert NXL
™
- 60Hz, UL version (Model 40) - Status and Coil
Data Label
Status
Coil
# of Bits
Notes
NXL Type
Battery Self Test
10082
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Low Shutdown
10092
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Shutdown - REPO
10093
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
UPS Output on Bypass
10129
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Output Load on Maint. Bypass
10132
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Main Battery Disconnect Open
10136
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Bypass - Excess Auto Retransfers
10147
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Battery Low
10152
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Shutdown - EPO
10157
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Output Off
10158
—
1
Active on Alarm
Deprecated
Battery Over Temperature
10172
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inlet Air Over Temperature
10173
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Input Current Imbalance
10185
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Input Phs Rotation Error
10191
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Rectifier Failure
10259
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inverter Failure
10263
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Main Controller Fault
10293
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Bypass Not Available
10321
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Overload Phase A
10322
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Overload Phase B
10323
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Overload Phase C
10324
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Auto Retransfer Failed
10325
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Static Switch Unavailable
10326
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Static Switch Overload
10327
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Excessive Pulse Parallel
10328
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Auto Transfer Failed
10329
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Frequency Error
10330
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass - Manual Rexfr Inhibited
10331
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass - Manual Xfr Inhibited
10332
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Static Switch Off Extrnl
10333
—
1
Active on Alarm
CE only
Battery Charging Reduced-Extrnl
10334
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Capacity Low
10335
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Discharging
10336
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Temperature Imbalance
10337
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Temperature Sensor Fault
10338
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Charging Inhibited
10339
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 1 Open
10340
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 2 Open
10341
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 3 Open
10342
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 4 Open
10343
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 5 Open
10344
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 6 Open
10345
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 7 Open
10346
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 8 Open
10347
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery - External Monitor 1
10348
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery - External Monitor 2
10349
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS