“P” Group: Expansion Card Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–64
“P” Group: Expansion Card Functions
The (optional) expansion card for the L200
2
 inverter has assiciated configuration data. 
The following table defines the functions and their value ranges. Please refer to the 
expansion card manual for more details.
NOTE: The “P” Group parameters do not appear in the parameter list shown on the 
keypad display unless the expansion card is installed on the inverter.
“P” Function
Run 
Mode 
Edit
Lo Hi
Defaults
Func.
Code
Name /
SRW Display
Description
–FE(F) 
(EU)
–FU 
(USA)
Units
P044
Network comm 
watchdog timer
Range is 0.00 to 99.99
✘ ✘
1.00
1.00
sec.
TIMER     01.00s
P045
Inverter action on 
network comm error
Five options:
00... Trip (Error Code E70)
01... Decelerate to stop and trip 
(Error Code E70)
02... Hold last speed
03... Free run stop
04... Decelerate and stop
✘ ✘
01
01
T-OUT        FTP
P046
Polled I/O output 
instance number
Three settings:
20, 21, 100
✘ ✘
21
21
O-AS-INS     021
P047
Polled I/O input 
instance number
Three settings:
70, 71, 101
✘ ✘
71
71
O-AS-INS     071
P048
Inverter action on 
network idle mode
Five options:
00... Trip (Error Code E70)
01... Decelerate to stop and trip 
(Error Code E70)
02... Hold last speed
03... Free run stop
04... Decelerate and stop
✘ ✘
01
01
IDLE         FTP
P049
Network motor poles 
setting for RPM
Range is 00 to 38 (even 
numbers only)
✘ ✘
0
0
P            00P