Hitachi L2002 Manual Do Utilizador

Página de 304
Using Intelligent Input Terminals
Oper
ations
and Monitor
ing
4–26
Three-wire Interface Operation
The 3-wire interface is an industry standard motor control interface. This function uses 
two inputs for momentary contact start/stop control, and a third for selecting forward or 
reverse direction. To implement the 3-wire interface, assign 20 [STA] (Start), 21 [STP] 
(Stop), and 22 [F/R] (Forward/Reverse) to three of the intelligent input terminals. Use a 
momentary contact for Start and Stop. Use a selector switch, such as SPST for the 
Forward/Reverse input. Be sure to set the operation command selection A002=01 for 
input terminal control of motor.
If you have a motor control interface that needs logic-level control (rather than momen-
tary pulse control), use the [FW] and [RV] inputs instead.
Option 
Code
Terminal 
Symbol
Function Name
Input 
State
Description
20
STA
Start Motor
ON
Start motor rotation on momentary contact (uses 
acceleration profile)
OFF
No change to motor operation
21
STP
Stop Motor
ON
No change to motor operation
OFF
Stop motor rotation on momentary contact (uses 
deceleration profile)
22
F/R
Forward/Reverse
ON
Select reverse direction of rotation
OFF
Select forward direction of rotation
Valid for inputs:
C001, C002, C003, C004, 
C005
Required settings:
A002 = 01
Notes:
The STP logic is inverted. Normally the switch will 
be closed, so you open the switch to stop. In this 
way, a broken wire causes the motor to stop 
automatically (safe design).
When you configure the inverter for 3-wire inter-
face control, the dedicated [FW] terminal is 
automatically disabled. The [RV] intelligent 
terminal assignment is also disabled.
Example (requires input configuration—
see page 
See I/O specs on page 
.
STP
STA
F/R
1
2
3
4
5
L
PCS