Frequency arrival output [FA1] uses the 
standard output frequency (parameter 
F001) as the threshold for switching. In 
the figure to the right, Frequency Arrival 
[FA1] turns ON when the output 
frequency gets within 0.5 Hz below or 
1.5 Hz above the target constant 
frequency. This provides hysteresis that 
prevents output chatter near the threshold 
value.The hysteresis effect causes the 
output to turn ON slightly early as the 
speed approaches the threshold. Then the 
turn-OFF point is slightly delayed. The 
timing is further modified by a small 
60 ms delay. Note the active low nature of 
the signal, due to the open collector output. 
Frequency arrival output [FA2] works the 
same way; it just uses two separate 
thresholds as shown in the figure to the 
right. These provide for separate acceler-
ation and deceleration thresholds to 
provide more flexibility than for [FA1]. 
[FA2] uses C042 during acceleration for 
the ON threshold, and C0043 during 
deceleration for the OFF threshold. This 
signal also is active low and has a 60 ms 
delay after the frequency thresholds are 
crossed. Having different accel and decel 
thresholds provides an asymmetrical 
output function. However, you can use 
equal ON and OFF thresholds, if desired.
FA1
signal
Output
freq.
60 ms
60 ms
ON
ON
t
0.5 Hz
0.5 Hz
1.5 Hz
1.5 Hz
0
t
F001
F001
FA2
signal
Output
freq.
t
ON
0.5 Hz
1.5 Hz
60 ms
accel.
decel.
Thresholds
60 ms
0
C043
C042