Terminal Function Explanation
Classi- 
fication
Terminal Code
Terminal Name
Explanation of Function
Output for 
Motor
FM
Analog Monitor
Outputs + 10VDC between FM and CM terminals. When 
frquency setting is equal to the maximum frequency setting, 
outputs + 10VDC at 150% current when monitoring output 
current.
• Two DC voltmeters (internal resistance of 10K ohm or 
greater) can be connected.
• In case of DC ammeter (1mA full scale), it is necessary to 
add series resistance of 10K ohm (1/2W)
• This output is a pulse output constant frequency (38. 1 Hz) 
which has a variable duty.
Contact 
Output
30A, B, C
Combined Alarm Output 
Terminals
Output via no volt signal (contact1c) to  indicate that the 
drive's protective function has been activated by an alarm.
• Contact capacity (DC48V.   0.3A)
C92-04