FVR-C9S-7UX
Terminal Function Explanation
Classi-
fication
Terminal Code
Terminal Name
Explanation of Function
Output for
Motor
FM
Analog Monitor
Outputs + 10VDC between FM and CM terminals. When
frquency setting is equal to the maximum frequency setting,
outputs + 10VDC at 150% current when monitoring output
current.
frquency setting is equal to the maximum frequency setting,
outputs + 10VDC at 150% current when monitoring output
current.
• Two DC voltmeters (internal resistance of 10K ohm or
greater) can be connected.
greater) can be connected.
• In case of DC ammeter (1mA full scale), it is necessary to
add series resistance of 10K ohm (1/2W)
add series resistance of 10K ohm (1/2W)
• This output is a pulse output constant frequency (38. 1 Hz)
which has a variable duty.
which has a variable duty.
Contact
Output
30A, B, C
Combined Alarm Output
Terminals
Terminals
Output via no volt signal (contact1c) to indicate that the
drive's protective function has been activated by an alarm.
drive's protective function has been activated by an alarm.
• Contact capacity (DC48V. 0.3A)
C92-04