Falcon SG1KRM-2TU Manual Do Utilizador

Página de 24
SG Series
TM
UPS PLUS
®
1kVA to 3kVA
22
 
Model Number  
SG1KRM -1TU 
SG1KRM -2TU 
SG2KRM -1TU 
SG2KRM-2TU 
SG3KRM-1TU 
SG3KRM-2TU 
Nominal VA  
1000 
2000 
3000 
        
 
Electrical Input  
Nominal AC Voltage  
120V 
230V 
120V 
230V 
120V 
230V 
AC Voltage Range  
87-140V 
170-275V 
87-140V 
170-275V 
87-140V 
170-275V 
Current-Amps   
6.9 
3.6 
14.2 
7.5 
21.4 
11.2 
Frequency
 
50/60 Hz  ± 5% (Auto–Tracking)
 
Power Factor Correction
 
> 0.95
 
Efficiency  (Typical)  
> 89% 
> 86% 
 
Electrical Output  
Watts 
700 
700 
1400 
1400 
2100 
2100 
AC Voltage    
(Switchable ) 
100V 
110V 
115V 
120V 
200V 
220V 
230V 
240V 
100V 
110V 
115V 
120V 
200V 
220V 
230V 
240V 
100V 
110V 
115V 
120V 
200V 
220V 
230V 
240V 
Frequency  
50/60 Hz (Auto Tracking ) 
Frequency Stability  
± 0.3% (Battery Mode)  
Voltage Regulation  
± 2% 
Step Load Change  
± 7% for 100% load variation  
Harmonic Dis tortion  
< 3% Linear Load, < 5% Non -Linear Load  
Overload  
105% load for 50 Seconds  
Crest Ratio  
3:1 
 
Battery 
DC Voltage  
48V 
72V 
96V 
Type 
12V, 7AH Sealed  Lead Acid  Maintenance -Free 
Back Up Time         @ Full Load  
                               @ 1/2 Load  
6 Minutes  
19 Minutes  
7 Minutes  
20 Minutes 
5.5 Minutes  
15 Minutes  
Recharge Time  
8 Hours to 90%  
Battery times are approximate.  
 
Transfer Time  
Line Fails/Recovers  
Zero 
UPS to Bypass or Reverse  
< 4ms 
After Overload  
Auto Transfer to UPS  
 
Electrical Connecti ons 
Input 
6’ Cord with  
5-15P 
6’ Cord with  
Schuko or  
6-15P 
6’ Cord with  
L5-20P 
6’ Cord with  
Schuko or   
6-15P 
6’ Cord with  
L5 -30P 
6’ Cord with  
Schuko or  
 L6-20P 
Output 
(4) 5-15R 
(4) IEC320  
(4) 5-15R 
(4) IEC 320  
(4) 5-15R 
(4) IEC 320  
Contact the factory fo r other input/output options. . 
 
Environmental  
Operating Temperature  
0º C - 40º C (32º F to 104º F)  
Humidity  
10% to 95% Non  – Condensing  
Altitude  
7,000 Feet  
Cooling  
Low Velocity Forced Air Fans  
Audible Noise @ 1  Meter 
< 55dBA  
 
Controls and Indicators  
LED 
Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery
 & Load Capacity Level  
Audible Alarms  
DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency,  High Temp. , Over Load, Fault Alarm  
Communications  
RS-232 Serial Port    (Bundled  UPSilon 2000 Software)  
 
Mechanical  
UPS Module  Dimensions  
Battery Pack Dimensions  
 H x W x  D                 Inches  (mm) 
3.51 x 16.8 x 17.7   (89 x 426.7 x 449.5)  
Internal to UPS Module  
3.51 x 16.8 x 17.7    (89 x 426.7 x 449.5)  
3.51 x 16.8 x 17.7   (89 x 4 26.7 x 449.5)   External to UPS Module  
2kVA & 3 kVA are (2) cabinet configuration, Hot Swappable  Batteries  
UPS Module Weight       lb. (kg)  
Battery Pack Weight      lb. (kg)  
39  (18) 
Internal  
29   (13) 
53  (24) 
29   (13) 
64   (29) 
Agency Listing  
UL 1778, CU L, 
FCC Class A  
CE
 available with 
Schuko plug only  
UL 1778, CUL,  
FCC Class A  
CE 
available 
with Schuko 
plug only
 
UL 1778, CUL,  
FCC Class A  
CE 
available 
with Schuko 
plug only
 
Falcon Electric, Inc. -  5106 Azusa Canyon Rd. -  Irwindale, CA 91706 -  800.842.6940 Fax 626.962.7720
www.falconups.com - email: sales@falconups.com
©
2003 Falcon
®
Electric, Inc.  All rights reserved. Falcon
®
and the Falcon Electric logo are registered trademarks of Falcon Electric, Inc.
All other brand names and trademarks are the property of their respective owners.
The information and specifications stated in this document are subject to change without notice. 
MD44010-1F      08-05-03
 
Available Options    
Option A  
60 Hz to 50 Hz Frequency Conversion  
Option B  
50 Hz to 60 Hz Frequency Conversion  
Option C 
SNMP/HTTP Network Card (Internal)  
Option D 
Standard Contact Closure Interface Card  
External Battery Packs  
Extended Run Time Battery  Packs (minutes to hours)  
Slide Rails  
Heavy Duty Roller Bearing Slide Rails for side mounting