Fuji Bikes 5000G11S/P11S Manual Do Utilizador

Página de 132
 
 
6-2
6-2 Alarm Reset 
 
To release the trip status, enter the reset command 
by pressing the        key on the keypad panel or 
inputting signal from the terminal (RST) of the control 
terminals after removing the cause of the trip.    Since 
the reset command is an edge operation, input a 
command such as !!OFF-ON-OFF!! as shown in 
Fig.6-2-1. 
 When releasing the trip status, set the operation 
command to OFF.  If the operation command is set 
to ON, inverter will start operation after resetting. 
 
 
 
 
 WARNING
 
If the alarm reset is activated with the operation signal ON, the inverter will restart suddenly, which 
may be dangerous.    To ensure safety, disable the operating signal when releasing the trip status. 
as accident may result. 
 
 
 
Reset command 
               
OFF                          ON                OFF 
 
Keypad panel display
                   
                           
             
Normal 
display 
                                                       
 Alarm display
         
(Operable)
Alarm output 
   
       
 OFF               ON              OFF
 
                                                       
                                                            Fig.6-2-1 
10ms or 
Trip 
RESET