GE Power Supply Manual Do Utilizador

Página de 21
 
OPM_GTU_19X_1K0_3K0_XUS_V014
 
18
 
GT-UL Series: User manual 1.2 (US)
 
Digital Energy
 GT Series
g
 
 
6.3.2 Battery 
replacement 
procedure) 
1.5kVA 
Remove front panel 
Unscrew two bolts of the 
battery terminal cover and remove it 
4 Unplug 
battery 
connectors 
Unscrew five bolts of the 
6 battery 
compartment 
cover 
 
and remove it 
Unscrew two bolts of 
 
battery fixer and remove it 
8  Pull out the battery set 
 
and renew it 
9 Assemble 
UPS 
 by 
reverse 
procedure. 
 
 
 
 
6.3.3 Battery 
replacement 
procedure) 
3kVA 
 
NOTE: The battery banks should be installed by service personnel. 
 
Remove front panel 
Unscrew two bolts of the battery compartment 
3  Remove battery cover  
4  Unscrew two bolts 
5/6  Remove stop holder and battery terminal 
7  Grasp the tag to pull out the battery sets. 
 Be 
careful, 
heavy 
weight! 
 
Notice not to let the battery set 
 
to drop in accident 
7  When you see the first warning label, 
 please 
disconnect 
all 
leads 
 
Continue horizontally pulling the battery set 1 
 
until you see the next warning label (See fig. 6-4) 
7a  Now you can easily release battery set 1! (Gently lift it up!) 
 
Put battery set 1 beside. 
7b Continue pulling out battery set 2.  
8  Unplug all connectors of batteries 
Renew the batteries and re-install them with reverse procedure. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
6.4  Recycling the UPS at the end of service life 
 
GE Digital Energy, in compliance with environment protection recommends that the 
UPS equipment, at the end of its service life, must be recycled conforming to the local 
applicable regulations.
 
Fig. 6.3 
Fig. 6.4
Fig. 6.2