Cooper Bussmann PS-EXP Manual Do Utilizador

Página de 4
POWERPATH™ NAC POWER SUPPLIES
Description
The  Wheelock  Series  PS-6  and  PS-8  are  24VDC,  filtered  and 
regulated,  supervised  remote  power  supply/battery  chargers  are 
used  for  supervision  and  expanded  power  driving  capability  of  Fire 
Alarm  Notification  Appliance  Circuits.   The  PS-6  provides  6  amps  of 
power  distributed  across  4  outputs,  while  the  PS-8  provides  8  Amps 
across    4  output.  In  addition  the  PS-8  provides  additional  room  in 
the  chassis  for  accessories  like  an  Addressable  Control  Module,  with 
mounting studs.
The  Power  Supplies  may  be  connected  to  any  12V  or  24V  (FWR  or 
DC) Fire Alarm Control Panel (FACP) by using a Notification Appliance 
Circuit  (NAC)  or  a “Dry  Contact”.  Primary  applications  include  NAC 
expansion  (supports  ADA  requirements)  and  auxiliary  power  to 
support system accessories. This unit provides filtered and regulated 
24VDC,  up  to  four  (4)  Class “B”,  two  (2)  Class “A”,  or  two  (2)  Class 
“B”  and  one  (1)  Class “A”  Notification  Appliance  Circuits. With  the 
optional  plug-in  PS-EXP  module  the  unit  supports  (8)  Class “B”  or 
(4)  Class “A”  Notification  Appliance  Circuits.  Additionally,  an  auxiliary 
power  output  of  2.5  Amps  (disconnected  upon  AC  power  loss  or  an 
alarm condition) or up to 0.240 A of constant power on the PS-8 and 
0.075 A of constant power on the PS-6.
The Wheelock Power Supplies can accommodate 7 or 12 AH batteries 
inside  its  lockable  chassis.  Using  an  external  battery  cabinet  it  can 
charge  up  to  33  AH  batteries  (pending  UL  testing).   Two  FACP  NAC 
circuits or two “Dry” contact initiating circuits can be connected to the 
inputs. These inputs can then be directed to control supervision and 
power delivery to any combination of the four (4) outputs. Each output 
is rated at 3.0 Amps (Class “B”) or (Class “A”) and can be programmed 
to  generate  a  steady  or  Code  3 Temporal  Horn  sound  and  a  strobe 
output  under  alarm  condition. Total  load  for  the  PS-6  and  PS-8  NAC 
circuits must not exceed the power supplies rated output.
The Power Suppliesunder non-alarm condition provides independent 
supervision  for  Class “A”  and  Class “B”  FACP  NAC  circuits.  In  the 
event of circuit trouble, the FACP will be notified via the POWERPATH 
steered  input  (IN1  or  IN2).  In  addition  there  are  two  sets  of  trouble 
reporting  terminals,  one  used  for  AC  power  loss  reporting  and  the 
other  for  all  troubles. The  AC  power  loss  reporting,  on  the  common 
trouble  terminals  and  on  IN1  or  IN2,  can  be  delayed  for  either  30 
seconds  or  170  minutes. The  AC  power  loss  terminals  will  always 
report the trouble within 1 second after loss of AC power.
PS-6
Approvals
• Approvals Include: UL Standard 864, 1481, California State  
   Fire Marshal (CSFM),  Factory Mutual (FM)
• Compliant with NFPA 72
Inputs
• 120VAC, 50/60Hz, 4.25 Amps (PS-6/8) and 5.32 Amps  
   (PS-8) Operating Power in Alarm 
• 240VAC, 60Hz, 2.42 Amps (PS-6E and 3.22 Amps (PS-8E) ‘
   Operating Power in Alarm
• 24VDC Battery Backup Connection
• Two (2), 12V or 24V NAC Initiating Circuits (8-33V at 5mA) 
FWR or DC
• Two (2) “Dry” Contact initiating Circuits
• Accepts two (2) Class “A” or two (2) Class “B” circuit inputs
• Built in battery charger for sealed lead acid or gel type 
batteries 
 
Outputs
• NAC outputs are 24VDC, 3.0 Amps each, power limited
• 8 Amps on PS-8 and 6 Amps on the PS-6 total alarm current 
...Features continued on next page
U
L
®
PS-8
Notification
The  PS-6  and  PS-8  Power  Supplies  are  UL  Listed  under  UL 
Standard  864,  9th  Edition  to  be  used  with  any  24  volt  Listed 
Regulated  notification  appliances. They  include  the  capability 
to  synchronize Wheelock  strobes  and  horns  and  to  silence  the 
horn signal when horn/strobes are operating on two wires. 
PS-EXP