HSM CMN4000R Manual Do Utilizador

Página de 16
 
 
T H E   C O N T I N U O U S   P O W E R   C O M P A N Y
 
Page 13 
SPECIFICATIONS 
ELECTRICAL 
Input CMN3000R/CMN4000R 
Voltage 
120V  +10%, -20% (without 
Battery discharge) 
Power Factor Corrected 
IAW MIL STD. 1399 Sec. 300 
Frequency 
45 to 65Hz 
Current(Amps) @ 120VAC 
21A/28A @ 100% Non-Linear 
Output 
Voltage 
120VAC 
± 3% 
Frequency 
50Hz / 60Hz (software select) 
Line Sync  (software select) 
Current(Amps) 
25A/33A @ 100% Non-Linear 
Crest Factor Ratio 
(Non-linear load and 
less than 5% THD) Typical 
@50% Load       Up to 4.8:1 
@75% Load       Up to 3.2:1 
@100% Load     Up to 2.4:1 
Total Harmonic Distortion (THD) 
3% Typ; 5% Max. 
(@100% Non-linear load) 
Dynamic Response 
±4% for 100% Step Load Change, 
0.5 Millisecond Recovery Time 
Overload 
110% for 10 Minutes; 
200% for 50 Milliseconds 
Efficiency (UPS) 
85-87% Typical 
UPS Protection 
Input and Output Short Circuit;  
Input and Output Overload;  
Excessive Battery Discharge 
ENVIRONMENTAL 
Operating Temperature 
0
o
C to 40
o
Humidity 
0% to 95% Non-condensing 
Altitude 
Sea Level to 10,000 Feet 
Audible Noise 
42 dBA at Five Feet 
MECHANICAL 
Input  
CPC Type 3 Position Inlet 
Connectors
 
Output (Qty.) 
Load 1 and Load 2 (3 each) 
NEMA Type 5-20R 
Cooling 
Low Velocity, Temperature 
Controlled Reversible Forced 
Air 
Dimensions: HxWXD In. 
5.25 x 19 x 23 
Weight: Lbs. (Kg) 
85 (38.8) 
 
 
 
DESIGN 
Standard Features 
Power Factor Corrected, Digital 
Regenerative
™ On-Line, Sinewave
Inverter Powers Load Continuously 
Extended Brownout Protection 
Designed for Non-linear Loads 
Continuous Operation on  
-25%,+12% Line 
Automatic Bypass 
RS232 Data Interface 
Software Selectable Output 
Frequency 
AC Output Switch 
Auxiliary Battery Connector 
Rear Mounted Ground Stud 
Optional SNMP Interface 
Specifications 
UL 1778, CUL, FCC Class A,  
IEEE 587/ANSI C62.41, 
IEC 555 @ 120VAC 
MTBF 
In Excess of 100,000 Hours 
CONTROLS AND INDICATORS 
Visual Indicators 
Sequenced LEDs 
Single LED 
 
Battery Level, Load Level 
AC Input, Inverter On, Load On 
Summary Alarm, Alarm Silence, 
Cold Start,  
Front Panel Controls 
Power On, Cold Start 
Alarm Silence, Battery Test 
AC Output On/Off, Bypass 
Audible Alarms 
Utility Interrupt, Inverter Failure 
Overload, Low Battery 
RS232 Data Interface  (DB-9F) 
Full Interactive, Remote Computer 
Monitoring and Control of UPS 
Functions. 
Compatible with Systems 
Enhancement
TM
 UPS Monitor & 
Control Software 
Open Collector (DB-9F) 
Allows Alarm Function Monitoring 
Optional SNMP Interface 
(RJ45 or BNC) 
Allows Full Control and Monitoring 
Over Network Connection. 
Specifications subject to change without notice