Sanyo E11A102A Manual Do Utilizador

Página de 46
 
− 16 − 
BATT
EXT.
MAIN SW
INPUT plug 
(seen from prong side) 
 
Note 
When the AC input power is single-wire
grounded, always connect the ground
phase to the S terminal (phase) side on
the UPS. 
 
7. Wiring 
 
 
CAUTION 
 
 
・ 
Check that input and output power plugs are firmly seated. Do not exceed the 
rated capacity when connecting loads to the output terminals. Check that 
plugs and cards are firmly seated in the external interfaces. Failure to observe 
these precautions can result in electric shock, fire, or bodily injury.   
・ 
The input power plug must be grounded. Failure to ground it can result in 
electric shock.   
 
 
7.1 UPS Wiring 
 
  Check that    MAIN SW    is in the “OFF” position. 
  Connect the INPUT power plug of the UPS to a   
utility power outlet. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The INPUT power plug is a 3-prong grounded type. 
If the utility power outlet is a 2-prong type (there is no ground terminal), use a 3-prong ground 
adapter such as WH2432P (Matsushita Electric) or ME2920 (Meikosha). 
Adapter wiring example 
  Switch is “OFF”. 
To 3-prong grounded 
utility power outlet 
E
Plate fixing screw 
Metal pipe 
Ground near 
power service 
entrance 
Metal box 
Adapter 
Ground 
lead wire 
Plate 
Length 1.8 m (7.09 inches)