Toshiba TOSVERT VF-FS1 Series Manual Do Utilizador

Página de 38
E6581373
- 19 -
6.4. Configuration 
properties
6.4.1. nciMaxSpeed
 
(
Maximum Speed
)
Configuration property (nc50), Variable Speed Drive 6010_11 (Mandatory)
SNVT type: SNVT_lev_percent (81)
SCPT reference: SCPTmaxSetpoint (50)
It is used to define the maximum speed of the inverter output. The value is entered as a percent of
nominal speed. The value of the maximum speed must be validated against the value of the minimum
speed as follows:
- Valid range:
0.000 % 
≤ minimum speed ≤ maximum speed ≤ 163.830 %
(Limited within the value of the inverter parameter “ul” limitation)
- Unit: 0.005%
- Default Value: 100.000%
N.B.: By editing this variable, this option unit changes the inverter parameter “ul”, automatically.
When setting small value, it may be limited by the lower limit of the inverter parameter “ul”
 Danger
Prohibited
Do not set the value out of valid range.
Setting the value out of valid range may result in injuries by motor running with
unexpected speed.
6.4.2. nciMinSpeed
 
(
Minimum Speed
)
Configuration property, Variable Speed Drive 6010_11 (Mandatory)
SNVT type: SNVT_lev_percent (81)
SCPT reference: SCPTminSetpoint (53)
It is used to define the minimum speed of the inverter output. The value is entered as a percent of
nominal speed. The value of the minimum speed must be validated against the value of the maximum
speed as follows:
- Valid range:
0.000 % 
≤ minimum speed ≤ maximum speed ≤ 163.830 %
(Limited within the value of the inverter parameter “ll” limitation)
- Unit: 0.005%
- Default Value: 0.000%
N.B.: By editing this variable, this option unit changes the inverter parameter “ll”, automatically.
 Danger
Prohibited
Do not set the value out of valid range.
Setting the value out of valid range may result in injuries by motor running with
unexpected speed.