UPS Connections
 
Standard Unit with 120V Transformer Module 
Figure 2 shows the standard unit, consisting of one 
electronics module and one battery module, with the 
addition of the 120V isolation transformer module. 
 
The modules do not have to be stacked for the unit to 
operate; however, if the modules are to be stacked 
please refer to the 1700 Series UPS user manual for 
instructions on interlocking modules. 
 
To connect the modules electrically follow these steps: 
1.  The power cord from the electronics module must be 
plugged into the output receptacle on the back of the 
transformer module (see figure 1). 
2.  The input power cord from the transformer module 
must be plugged into a power source (see figure 1). 
 
The battery power cord must also be plugged into the 
electronics module for the system to provide backup 
power (refer to the 1700 Series UPS user manual or the 
battery module installation instructions for instructions on 
connecting the battery module). 
 
Note:  No more than three modules should be stacked 
in any configuration.  If the transformer module is being 
used with a system that has an expansion battery 
module at least one module must be placed beside the 
others.  Stacking four modules could result in a tipping 
hazard. 
 
Standard Unit with 230V Transformer Module 
Figure 3 shows the standard unit, consisting of one 
electronics module and one battery module, with the 
addition on the 230V IO transformer module. 
 
The modules do not have to be stacked for the unit to 
operate; however, if the modules are to be stacked 
please refer to the 1700 Series UPS user manual for 
instructions on interlocking modules. 
 
To connect the modules electrically follow these steps: 
1.  Plug the output power cord from the transformer 
module into one of the output receptacles on the 
back of the electronics module (in the case of the 
2.4kVA model the cord can only be plugged into the 
20A outlet, see figure 1). 
2.  Next, plug the power cord from the electronics 
module into the output receptacle on the back of the 
transformer module (see figure 1). 
3.  The input power cord from the transformer module 
must be plugged into a power source (see figure 1). 
 
The battery power cord must also be plugged into the 
electronics module for the system to provide backup 
power (refer to the 1700 Series UPS user manual or the 
battery module installation instructions for instructions on 
connecting the battery module).  The unused 
receptacles on the back of the electronics module are 
still active, but they are providing 120V power, not 230V.  
All 230V power must be drawn from the output 
receptacles on the back of the transformer module. 
Figure 2 :  120V Transformer Module Configuration 
Figure 3:  230V Transformer Module Configuration