Instruction Manual for the Eaton RTC-50 
Automatic Transfer Switch Controller
SECTION 4:  PROGRAMMING
4.1  Introduction
The RTC-50 controller is programmable via the two programming 
jumpers shown in Figure 2.  
The TDNE jumper enables the end-user to select a Time Delay Nor-
mal to Emergency setting of either 20 seconds or 50 seconds.  
TDNE is a time delay that starts timing when the Generator source 
becomes available either after the Utility becomes unavailable or 
after the Go To Generator input is activated.  The 50 second set-
ting may be used to allow for a longer warm-up period of the Gen-
erator.
The FREQ jumper enables the end-user to program the RTC-50 for 
an operating frequency of either 50 or 60 hertz.
Figure 2. RTC-50 Programming Jumpers.
Table 2 is a summary of the Fixed and Jumper-selectable settings that are available in the RTC-50.
Table 2. Fixed and Jumper-Selectable Settings
DESCRIPTION
RANGE
FACTORY DEFAULT
FIXED/JUMPER
Time Delay Normal to Emergency 
20 or 50 seconds 
20 seconds
Jumper-selectable
Time Delay Emergency to Normal 
10 seconds 
10 seconds Fixed 
setting
Time Delay Emergency Fail Timer 
6 seconds 
6 seconds
Fixed setting
Nominal Frequency 
50 or 60 Hz 
60 Hz
Jumper-selectable
Nominal Voltage 
240 Vac 
240 Vac 
Fixed setting
Utility Undervoltage Dropout 
70% of 240 Vac Nominal Voltage
70% of 240 Vac Nominal Voltage
Fixed setting
Generator Undervoltage Dropout 
70% of 240 Vac Nominal Voltage
70% of 240 Vac Nominal Voltage
Fixed setting
Utility Undervoltage Pickup 
80% of 240 Vac Nominal Voltage
80% of 240 Vac Nominal Voltage
Fixed setting
Generator Undervoltage Pickup 
80% of 240 Vac Nominal Voltage 
80% of 240 Vac Nominal Voltage
Fixed setting