Connecting up 
 
4.2 Power supply 
SCALANCE XB-200 
Operating Instructions, 02/2015, C79000-G8976-C359-01 
25
 
4.2 
Power supply 
Notes on the power supply 
 
 
WARNING 
Incorrect power supply 
Never operate the device with AC voltage or DC voltage higher than 32 V DC. 
 
 
CAUTION 
Damage to the device due to overvoltage 
The connector of the external power supply is not protected against strong electromagnetic 
pulses that can, for example, result from lightning strikes or switching large loads. 
One of the tests used to attest the immunity of devices of the SCALANCE CB-200 IE 
switches to electromagnetic interference is the "surge immunity test" according to 
EN61000-4-5. This test requires overvoltage protection for the power supply lines. A 
suitable device is, for example, the Dehn Blitzductor BVT AVD 24, article number 918 422 
or a comparable protective element. 
Manufacturer: DEHN+SOEHNE GmbH+Co.KG, Hans-Dehn-Str.1, Postfach 1640, D92306 
Neumarkt, Germany 
Operate the SCALANCE XB-200 with suitable overvoltage protection. 
 
Information on the power supply 
●  The power supply is connected using a 3-pin plug-in terminal block (spring-loaded 
terminal). The terminal block ships with the device and can also be ordered as a spare 
part. 
●  The power supply can be connected redundantly. Both inputs are isolated. There is no 
distribution of load. 
●  The power supply is connected over a high resistance with the enclosure to allow an 
ungrounded set up. The two power inputs are non-floating. 
●  To wire up the power connector, use a copper cable of category 24-16 AWG or a cable 
with a cross-section of 0.25 to 1.5 mm². 
●  To wire up the functional ground, use a copper cable of category 20-16 AWG or a cable 
with a cross-section of 0.75 to 1.5 mm².