SOLID CORE AND SPLIT CORE ADJUSTABLE CURRENT “STATUS” SWITCHES
62-0242—01
2
Fig. 2. Sensor removed from DIN rail
Fig. 3. Wires through sensors
WARNING
The secondary of the 5 Amps Current 
Transformer must be shorted together before 
the power may be turned on to the monitored 
device.
For applications in which the normal operating current is 
greater than 250 Amps or for conductor diameters larger 
that 3/4 in. (19 mm) in diameter, and external 5 Amps 
Current Transformer (C.T.) must be used as shown in 
Fig. 4.
Fig. 4. Current transformer
Latch Operation
Pressing down on the two (2) side tabs and swinging the 
cover open opens the split core current switch as shown 
in Fig. 5. Lifting up the latch with a flat-tip screwdriver as 
shown in Fig. 6 can also open the unit. Press down firmly 
on the cover to close the current switch. An audible “click” 
will be heard as the tab slides over the tongue on the 
base.
CAUTION
Mating surfaces of the magnetic core are 
exposed when the sensor is open. Silicone 
grease, present on the cores to prevent rust, 
can capture grit and dirt if care is not 
exercised. Operation can be impaired if 
anything prevents good contact between pole 
pieces. Visually check the mating parts of the 
core before closing the current sensor.
Fig. 5. Opening sensor by hand
3X
M25290
C
R
U
L
U
S
M25291
U
R
C
L
US
U
R
C
L
US
EXAMPLE:  FOR CURRENTS UP TO 600 AMPS, USE A 600:5 RATIO C.T.
 AS 
SHOWN. 
INSULATED         CONDUCTOR
600:5 RATIO 5A C.T. 
WIRE NUT 
M25295A
C
U
R
L
US
C
US
R
U
L
M25298