Liebert POWER PROTECTION STATIC TRANSFER SWITCH Manual Do Utilizador

Página de 152
Power and Control Wiring
12
5.5
Remote Source Selection Wiring
An optional Remote Source Selection board may be installed in your STS2. This board is installed in 
the same bay as the communications options. See Figures 21 and  22 for the location of these options. 
See Figure 23 for information on the control wiring for the Remote Source Selection option.
The Remote Source Selection allows you choose the preferred input source from a remote location. 
Terminal connections allow the customer to remotely select a source to be the preferred source in the 
same process as the local source transfer selection. 
The unit’s preferred source selection and Remote Source Selection are active at the same time, with 
the STS2 following the last request for a preferred source change, regardless of whether it was from 
the local or Remote Source Selection controls.
A six pin terminal block provides the Remote Source Selection connections. Two pairs of wires are 
used from the switch to trigger the source selection. You can select the type of switch used for this 
remote control. Connections are made to four of the connections, using Form A dry contacts. The con-
tacts are numbered left to right:
See 10.3 - Enabling Remote Source Selection for instructions on enabling the Remote Source 
Selection option.
5.6
Power Supply
The STS2 is supplied with redundant power supplies that are designed to operate from a voltage 
range of 200V to 600V. The unit is set at the factory to match the nameplate voltage. Field adjust-
ments are not necessary. If the unit needs to operate at a voltage other than what is listed on the 
nameplate, contact Liebert Global Service or the local Liebert representative. Table 7 provides trans-
former tap information.
Table 6
Remote source selection terminal block
Contact
Connection
1
Source 1
2
Isolated ground
3
Source 2
4
Isolated Ground
5
DO NOT USE
6
DO NOT USE
Table 7
Terminal block 1 and terminal block 2 wire connections
Voltage
Connect t
Connect
Jumper 
Between
F1
TB1-XX
F2
TB1-YY
F3
TB2-XX
F4
TB2-YY
200
1
9
1
9
1-7
208
1
10
1
10
1-7
220
2
12
2
12
6-8
240
1
11
1
11
1-7
380
1
8
1
8
2-7
400
1
9
1
9
3-7
415
1
10
1
10
4-7
480
1
11
1
11
5-7
600
1
12
1
12
6-7
!
CAUTION
Using Table 7, ensure that the wiring for the control transformers matches the input voltage 
for the unit.
Improper wiring could result in blown fuses.