Installation Drawings
30
Figure 18 Electrical field connections drawing: 800 – 1000 amp STS2 with single output breaker
SECTION A-A
SIDE VIEW
(WITH FRONT PANELS REMOVED)
FRONT VIEW
FRONT VIEW
GROUND BUS
.51 DIA.
  NEUTRAL BUS
RIGHT SIDE VIEW
.51 DIA.
INPUT/OUTPUT BUS
 RIGHT SIDE VIEW
NEUTRAL   BUS
GROUND
 BUS
Ø A, Ø B, Ø 
C
SYSTEM OUTPUT
Ø A, Ø B, Ø C
SOURCE 1 INPUT
CB5
CB3
CB2
CB1
CB4
SOURCE 1 INPUT Ø 
A
SOURCE 2 INPUT
Ø A, Ø B, Ø C
SOURCE 1 INPUT Ø 
B
SOURCE 1 INPUT Ø C
PEM NUT
FRONT
  BUS
NEUTRAL
CB3
SYSTEM OUTPUT 
ONE-LINE DIAGRAM
PS212800 Rev. 2
CB4
K3
K2
K1
CB5
K3
K1
K2
SOURCE 1
CB1
SOURCE 2
CB2
NOT 
RECOMMENDED.
NOTES:
1. ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS).
5. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL
4. 
ALUMINUM 
AND 
COPPER 
CLAD ALUMINUM CABLES ARE
3. CONTROL WIRING AND POWER WIRING MUST BE RUN
2. TOP AND BOTTOM CABLE ENTRY AVAILABLE THROUGH
AND LOCAL ELECTRICAL CODES.
RUN IN A SEPARATE CONDUIT FROM INPUT CABLES.
IN SEPARATE CONDUIT. OUTPUT CABLES SHOULD BE 
CONDUIT SIZE, AND REPLACE.
REMOVABLE ACCESS PLATES. REMOVE, PUNCH TO SUIT
NEUTRAL, AND GROUND CABLE CONNECTIONS. KIT
6. HARDWARE KIT IS SUPPLIED FOR INPUT, OUTPUT,
INCLUDES 1/2" BOLTS, WASHERS, AND NUTS FOR CONNECTING 
CABLES TO THE BUS BARS.
7. THE TORQUE REQUIREMENT FOR 1/2"-13 PEM NUTS IS 428 INCH-LBS. (48 N-m).