FRU Removal and Replacement
If an event code 513 does not appear in the log, go to 
 on page 3-6 to isolate the problem.
7. At the EFC Server’s Hardware View:
a. Ensure no alert symbols appear that indicate a failure (yellow 
triangle or red diamond).
b. Click the port graphic representing the replacement SFP to 
open the Port Properties dialog box. Verify that port 
information (port number, port name, operational state, and 
port technology) is correct. 
If a problem is indicated, go to 
to isolate the problem.
8. Restore communication to the port and set the port online as 
directed by the customer (
9. Perform the data collection procedure (
10. Clear the switch’s system error (ERR) LED:
— If at the EFC Server, open the  Hardware View and:
a. Right-click the front panel bezel graphic (away from a FRU) to 
open a pop-up menu.
b. Click Clear System Error Light.
— If at a web browser connected to the SANpilot interface:
a. Click the Switch tab at the Operations panel. The Operations 
panel opens with the Switch page displayed.
b. Click the Sys Err Light tab. The Switch page displays with the 
Sys Err Light tab selected. A System Error Light is ON 
message displays on the page.
c. Click Clear Light.
RRP: Power Supply
Use the following procedures to remove or replace a power supply 
from the rear of the switch. No tools are required.
Removal
To remove a power supply: