Event Code Tables
Power Supply Events (200 through 299)
Event Code: 200
Message:
Power supply ac voltage failure
Severity:
Major
Explanation:
Either the ac input to the indicated power supply has been lost, or the ac voltage has failed in the power supply
module. This event can only occur when dual power supplies are installed. The second supply automatically
assumes the full load to continue providing uninterrupted system power.
module. This event can only occur when dual power supplies are installed. The second supply automatically
assumes the full load to continue providing uninterrupted system power.
Action:
Ensure that the power cord is securely connected to the receptacles at both ends, and verify the ac source is live.
If the ac voltage does not recover (recovery is indicated by event 203), replace the faulty power supply. Perform
the data collection procedure for this unit using the EFC Manager, save the data file to the EFC Manager Zip
drive, and return the CD and the faulty power supply to McDATA for analysis and repair.
If the ac voltage does not recover (recovery is indicated by event 203), replace the faulty power supply. Perform
the data collection procedure for this unit using the EFC Manager, save the data file to the EFC Manager Zip
drive, and return the CD and the faulty power supply to McDATA for analysis and repair.
Event Data:
No supplementary data included with this event.