CTP Card Events (400 through 499)
B-31
Event Code Tables
CTP Card Events (400 through 499)
Event Code: 400
Message:
Power-up diagnostics failure
Severity:
Major
Explanation:
The CTP power-on self test diagnostics detected a faulty FRU as indicated in the event data.
Action:
Replace the faulty FRU with a functional FRU. Perform the data collection procedure for the switch using the EFC
Manager, and return the CD and the faulty FRU to McDATA for analysis and repair.
Manager, and return the CD and the faulty FRU to McDATA for analysis and repair.
Event Data:
Byte 0: FRU code:
01 = LBA
02 = CTP
03 = SBAR
05 = Fan module
06 = Power supply
08-0F = Port module
02 = CTP
03 = SBAR
05 = Fan module
06 = Power supply
08-0F = Port module
Byte 1: Slot position
Byte 2: Device ID
Byte 3: Power-up error code (Internally defined) (stored in the faulty FRU EEPROM for analysis)
Bytes 4-7: Power-up data code (Internally defined) (stored in the faulty FRU EEPROM)
Byte 2: Device ID
Byte 3: Power-up error code (Internally defined) (stored in the faulty FRU EEPROM for analysis)
Bytes 4-7: Power-up data code (Internally defined) (stored in the faulty FRU EEPROM)
Distribution:
Switch
EFC Server
Host
Nonvolatile
System
Event Log
System
Error
Indicator
Event Log
E-Mail
Call-Home
Sense Info
Link Incident
✔
✔
✔
✔
✔
✔