IBM Type 8720 Manual Do Utilizador

Página de 180
Table
 
6.
 
Troubleshooting
 
charts
 
(continued)
 
Device
 
Suggested
 
action
 
Updating
 
the
 
switch-module
 
configuration
 
through
 
the
 
switch
 
does
 
not
 
save
 
the
 
management-module
 
NVRAM.
 
If
 
you
 
log
 
in
 
to
 
the
 
Ethernet
 
switch
 
module
 
directly
 
(through
 
the
 
Ethernet
 
switch-module
 
Web
 
interface
 
or
 
Telnet
 
interface
 
instead
 
of
 
through
 
the
 
management
 
module
 
Web
 
interface)
 
and
 
update
 
the
 
switch
 
module
 
configuration,
 
saving
 
the
 
new
 
configuration
 
saves
 
only
 
to
 
the
 
switch
 
NVRAM,
 
not
 
to
 
the
 
management-module
 
NVRAM.
 
The
 
management
 
module
 
will
 
not
 
be
 
able
 
to
 
communicate
 
with
 
the
 
switch
 
module.
 
In
 
the
 
management
 
module
 
Web
 
interface,
 
in
 
Switch
 
Tasks
 
 
Management,
 
change
 
the
 
New
 
Static
 
IP
 
Configuration
 
values
 
to
 
match
 
the
 
ones
 
in
 
Current
 
IP
 
Configuration,
 
and
 
apply
 
the
 
configuration.
  
Light
 
path
 
diagnostics
 
LEDs
 
A
 
system-alarm
 
LED
 
on
 
the
 
system
 
LED
 
panel
 
is
 
lit
 
when
 
certain
 
system
 
errors
 
occur.
 
If
 
one
 
of
 
the
 
system-alarm
 
LEDs
 
on
 
your
 
BladeCenter
 
T
 
unit
 
is
 
lit,
 
use
 
the
 
following
 
table
 
to
 
help
 
determine
 
the
 
cause
 
of
 
the
 
error
 
and
 
the
 
action
 
you
 
should
 
take.
 
Note:
  
You
 
can
 
configure
 
the
 
major
 
and
 
critical
 
alarm
 
LEDs
 
to
 
be
 
either
 
amber
 
or
 
red
 
through
 
the
 
management
 
module.
 
Table
 
7.
 
Light
 
path
 
diagnostics
 
Lit
 
LED
 
Cause
 
Action
 
BladeCenter
 
T
 
system
 
LED
 
panel
 
Location
 
A
 
condition
 
has
 
occurred
 
in
 
the
 
BladeCenter
 
T
 
unit
 
that
 
has
 
caused
 
the
 
remote
 
system
 
management
 
to
 
identify
 
the
 
BladeCenter
 
T
 
unit
 
as
 
needing
 
attention.
 
Look
 
for
 
any
 
information
 
or
 
error
 
LEDs
 
on
 
the
 
system
 
LED
 
panels,
 
the
 
modules,
 
and
 
the
 
blade
 
servers
 
in
 
this
 
BladeCenter
 
T
 
unit,
 
and
 
follow
 
the
 
instructions
 
in
 
this
 
table
 
for
 
those
 
LEDs.
 
Minor
 
A
 
noncritical
 
event
 
has
 
occurred
 
that
 
should
 
be
 
looked
 
at,
 
such
 
as
 
the
 
wrong
 
I/O
 
module
 
inserted
 
in
 
a
 
bay,
 
or
 
power
 
needs
 
that
 
exceed
 
the
 
capacity
 
of
 
power
 
modules
 
currently
 
installed.
 
Check
 
the
 
error
 
log
 
for
 
the
 
messages.
 
Check
 
the
 
LEDs
 
on
 
the
 
BladeCenter
 
T
 
unit
 
and
 
the
 
blade
 
servers
 
to
 
isolate
 
the
 
component.
 
Major
 
A
 
major
 
system
 
error
 
has
 
occurred,
 
such
 
as
 
the
 
loss
 
of
 
one
 
of
 
two
 
mirrored
 
disks.
 
Note:
 
You
 
can
 
configure
 
the
 
major
 
error
 
LED
 
to
 
be
 
either
 
red
 
or
 
amber
 
through
 
the
 
management
 
module.
 
v
   
Check
 
the
 
error
 
log
 
for
 
messages.
 
v
   
Look
 
for
 
an
 
error
 
LED
 
on
 
the
 
modules
 
and
 
blade
 
servers
 
to
 
locate
 
the
 
component:
 
   
If
 
the
 
error
 
LED
 
is
 
on
 
a
 
module,
 
follow
 
the
 
instructions
 
for
 
the
 
module
 
in
 
this
 
table.
 
   
If
 
the
 
error
 
LED
 
is
 
on
 
a
 
blade
 
server,
 
see
 
the
 
documentation
 
that
 
comes
 
with
 
the
 
blade
 
server.
 
 
98
 
BladeCenter
 
T
 
Type
 
8720
 
and
 
8730:
 
Hardware
 
Maintenance
 
Manual
 
and
 
Troubleshooting
 
Guide