With 4 power supply units, you must connect units 2 and 3 to the first 
source (phase) and units 5 and 6 to the second. Thus 2+2 redundancy is 
supported; the system continues to run if one source fails, provided the 
remaining 2 power supplies are sufficient to deliver the required power.
Power system with 3 AC sources (phases) available
With 6 power supply units, you must connect units 1 and 4 to the first AC 
source (phase), units 2 and 5 to the second, and units 3 and 6 to the third. 
Thus 4+2 redundancy is supported; the system continues to run if one 
source fails, provided the remaining 4 power supplies are sufficient to 
deliver the required power.
With 3 power supply units, you must connect each one to a different 
source. Thus 2+1 redundancy is supported; the system continues to run 
if one source fails, provided the remaining 2 power supply units are 
sufficient to deliver the required power.