FS-X20 Series FieldServer Start-up Guide (07-2005) 
2.  Product Description 
2.1.  Specifications  
Power requirements (power supply is external) 
X20 power supply P/N 69155 
Input voltage: 9-30VDC, 8W; 24VAC Floating.  Voltage variation of ±10% tolerated. 
Output voltage / current: 24VDC @ 0.5A 
Physical Dimensions(excluding the external power supply) 
(WxDxH): 
3.82 x 4.08 x 1.7 inches (9.70 x 10.36 x 4.31 cm) 
Weight: 
0.8 lbs. (0.36 Kg) 
Available Ports 
1 x RJ45 / RS-232 serial connector 
1 x RS-485 serial connector 
1 x RJ45 10-BaseT Ethernet connector 
Environment: 
Operating Temperature:  
0 – 60°C (32 – 140°F) 
Humidity: 
10 - 90% RH  (non-condensing) 
Approvals: 
UL 916 
ULC 916 
FCC Tested to comply with FCC part 15 
CE Marked  
(Specifications subject to change without notice) 
2.2.  Mounting 
The  FS-X20  Series  FieldServer  is  supplied 
with  an  accessory  bag  which  allows 
selection of adhesive feet (for standing on a 
shelf)  or  mounting  plates  for  wall  or  panel 
mount.    A  DIN  Rail  Mounting  Kit  (P/N  FS-
8915-28) may be ordered separately. 
 
2.3.  Wiring 
The  110VAC  to  9VDC  or  24VDC/  power 
supply  received  with  the  unit  needs  to  be 
plugged  into  a  power  source  and  then 
connected  to  the      back  of  the  FieldServer 
using the SPA59136 connector.  This power 
supply is designed to temporarily provide the 
9-24V  100mA  required  by  the  FieldServer 
during  testing  and  start-up.    Permanent  9-
30V, 100mA power will need to be provided 
for continuous operation. 
 
The  FS-X20  Series  FieldServer  is  shipped 
as  either  a  FS-X20XX-01  in  which  case  the 
RS-232 port is activated, or as a FS-X20XX-
02  in  which  case  the  RS-485  port  is 
activated.  
 
If  using  an  RS-232  RJ45  Serial  connection 
then use one of the RJ45 cables to connect 
from the appropriate port on the FieldServer 
to  the  connection  adapter  provided  with  the 
FieldServer or the Driver Kit.  Then plug the 
connection adapter to the node. 
 
If  using  RS-485  from  the  node  to  the  FS-
X2010, the + and - wire connections can be 
used on the RS-485 port on the FieldServer.  
For  the  FS-X2011,  LonWorks
®
  enabled 
modules,  the  orange  port  is  the  TP/FT-10 
connection,  and  the  RS-485  connection 
needs to be made via  the  serial  RJ-45 port.  
To  change  between  RS-232  and  RS-485 
connection,  it  is  necessary  to  modify 
jumpers  on  the  internal  board.    Refer  to 
eNote0017
2
 for further information. 
 
Ethernet 
connections 
simply 
require 
connection of a standard Cat5 UTP Ethernet 
cable  with  an  RJ45  connector  between  the 
FieldServer  and  the  network.    Note  that 
when  connecting  the  FieldServer  directly  to 
another  Ethernet  enabled  device  without 
using  a  hub,  then  standard  Ethernet 
principles  apply,  and  a  Crossover  cable 
must be used. 
 
Note that the USB port is not activated. 
                                                 