GE BECCO2200 Manual Do Utilizador

Página de 61
Restricted A164-0CG-1.00-2 
 
Full 
 
9 
 
Chapter 4: Configuring the A164PORT 
Table 
This chapter describes the configurable parameters in the Communication Port Configuration 
Table (A164PORT). 
4.1 General 
Information 
The A164PORT table provides information for the operation of the BECO2200 DCA’s 
communication port(s). One record is required for every communication port configured. 
4.2  Description of Fields 
Where applicableTable 4 describes the field name, range, special case, and typical value for 
each field of the A164PORT table. Following the table is a textual description of each field’s 
meaning. 
Table 4  BECO2200 DCA A164PORT Configuration Table 
Field 
Range 
Special 
Typical 
Communication Port 
Name 
COM1..COM9 
COMA..COMZ 
COM0 is typically reserved for 
WESMAINT 
COM1 
Communication Port 
Parity 
0 = None 
1 = Even 
2 = Odd 
N/A 
1 = Even Parity 
Baud rate 
110, 300, 600, 1200, 
2400, 4800, 9600 
N/A 
4800 or 9600 
RTS On Time 
0..65535 
Must be at least 1 if modem 
signals are used 
N/A