Non-fatal errors cause the offending process to log a message to the WESMAINT Error Log and
suspend without affecting the rest of the BECO2200 DCA. For example, if a single polling
process encounters a non-fatal error, no polling will occur on the associated communication port.
However, demand scans on the communication port will still be an available option.
This section contains a description of all these non-fatal errors. Expressions in angular brackets
like “<x>”, are filled with the appropriate values by the BECO2200 DCA. Each non-fatal error
message contains a unique identification number, within the range of E300 through E499.
E300: PORT rec <x>, invalid baud rate
Cause:
suspend without affecting the rest of the BECO2200 DCA. For example, if a single polling
process encounters a non-fatal error, no polling will occur on the associated communication port.
However, demand scans on the communication port will still be an available option.
This section contains a description of all these non-fatal errors. Expressions in angular brackets
like “<x>”, are filled with the appropriate values by the BECO2200 DCA. Each non-fatal error
message contains a unique identification number, within the range of E300 through E499.
E300: PORT rec <x>, invalid baud rate
Cause:
•
Record <x> of the A164PORT table contains an invalid Baud Rate.
Effect:
•
Communication to all BECO2200 devices configured to use this port will be unavailable.
Remedy:
•
Review the section on configuring the A164PORT table (Chapter 4:), and verify that the
Baud Rate configuration parameter is configured as either 110, 300, 600, 1200, 2400, 4800,
or 9600.
Baud Rate configuration parameter is configured as either 110, 300, 600, 1200, 2400, 4800,
or 9600.
E301: PORT rec <x>, invalid failures before offline
Cause:
•
Record <x> of the A164PORT table contains an invalid Failures Before Offline.
Effect:
•
Communication to all BECO2200 devices configured to use this port will be unavailable.
Remedy:
•
Review the section on configuring the A164PORT table (Chapter 4:), and verify that the
Failures Before Off-line configuration parameter is greater than zero.
Failures Before Off-line configuration parameter is greater than zero.
E302: PORT rec <x>, num of devices exceeds UNIT
Cause:
Cause:
•
The Number of Devices on Port parameter in record <x> of the A164PORT table is greater
than the number of records in the A164UNIT table.
than the number of records in the A164UNIT table.
Effect:
•
Communication to all BECO2200 devices configured to use this port will be unavailable.
Remedy:
•
Review the section on configuring the A164PORT table (Chapter 4:), and verify that the
Number of Devices on Port is correct.
Number of Devices on Port is correct.