SOLID CORE AND SPLIT CORE 4-20 MA OUTPUT CURRENT SENSORS
62-0245—01
2
WARNING
The secondary of the 5A Current Transformer 
(C.T.) must be shorted together before the 
power may be turned on from the device. 
For applications in which the normal operating current is 
greater than 200 or 250 Amps, depending on the model,  
or for conductor diameters larger than 0.75 in. (19 mm) in 
diameter, an external 5 Amp Current Transformer (C.T.) 
must be used in conjunction with a CTS20-005 or CTS20-
005VFD as shown in Fig. 5.
 
Fig. 3. Current transformer
Latch Operation (Split Core Models)
Pressing down on the two (2) side tabs and swinging the 
cover open, opens the split core current switch as shown 
in Fig. 6. Lifting up the latch with a flat-tip screwdriver as 
shown in Fig. 7 can also open the unit. Press down firmly 
on the cover to close the current switch. An audible “click” 
will be heard as the tab slides over the tongue on the 
base.
CAUTION
Mating surfaces of the magnetic core are 
exposed when the sensor is open. Silicone 
grease, present on the cores to prevent rust, 
can capture grit and dirt if care is not 
exercised. Operation can be impaired if 
anything prevents good contact between pole 
pieces. Visually check the mating parts of the 
core before closing the current sensor.
Fig. 4. Opening sensor by hand
Fig. 5. Opening with a screwdriver
Wiring
Honeywell recommends the use of 16 to 22 AWG (1.3 to 
0.3 mm
2
) shielded cable, copper wire only for all current 
sensor applications. A maximum wire length of less than 
98.4 feet (30 meters) should be used between the current 
sensors and the Building Management System or 
controller.
NOTE: When using a shielded cable, be sure to connect 
only (1) end of the shield to ground at the 
controller. Connecting both ends of the shield to 
ground may cause a ground loop.
When removing the shield from the sensor end, make 
sure to properly trim the shield so as to prevent any 
chance of shorting. The current sensor terminals are 
polarity sensitive and represent a linear and proportional 
4 to 20 mA output signal. The current sensors are 
available in either an Average or True RMS output 
version. The recommended torque to be used on the 
terminal block connections is 5.93 in-lbs (0.67 Nm). The 
EXAMPLE:  FOR CURRENTS UP TO 600 AMPS, USE A 600:5 RATIO C.T.
 AS 
SHOWN. 
INSULATED         CONDUCTOR
600:5 RATIO 5A C.T. 
WIRE NUT 
M25295A