Honeywell H Manual Do Utilizador

Página de 8
T7047C,G,H REMOTE SPACE SENSORS
62-0179
4
Fig. 6. T7047G1000 Remote Sensor resistance 
change with change in temperature.
Fig. 7. T7047H1008 Remote Sensor resistance 
change with change in temperature.
Wiring
IMPORTANT
All wiring must agree with applicable codes, 
ordinances and regulations.
Fig. 8 through 16 show schematics and typical 
connections. Also refer to instructions supplied with other 
system components.
IMPORTANT
To avoid electrical interference, which can 
cause erratic performance, keep wiring runs as 
short as possible and do not run wires adjacent 
to the line voltage electrical distribution 
systems. Use shielded cable (Belden type 8762 
or equivalent for 2-wire and Belden type 8772 or 
equivalent for 3-wire). The cable shield must be 
grounded only at the controlled equipment 
case.
Fig. 8. Internal schematic and typical 
wiring for T7047C1009.
Fig. 9. T7047C1025 connected to W960 or W927 
panel with internal setpoint adjustment.
Fig. 10. Two T7047C1025 Sensors and one 
T7047G1000 Sensor providing a 
temperature-averaging network for a 
T7300/Q7300 Thermostat/Subbase.
Fig. 11. Typical wiring for T7047H1008 to 
Excel 80/100/500/600 Controller.
1000 
900
800
700
600
500
10 
20
30
40
50
60 
70
80
90
100
RESISTANCE
(OHMS) 
710 OHMS AT
     75 F (24 C)
TEMPERATURE (DEGREES) 
M5354
-10 
0 10 20 30 40 
 C
 F
110
RESISTANCE
(OHMS)
1400
1317
1231
1145
1059
973
20
40
60
80
100
120
140
160
180
200
220
-7
0
10
20
30
40
50
60
70
80
90
100
F
C
1093 OHMS AT
75  F (24  C)
M10020
TEMPERATURE (DEGREES)
T1
T2
4
R
B
W
1
T1
T
T
M3383
S963B1003
REMOTE SETPOINT
POTENTIOMETER
M7044 OR
M7045 MOTOR
TO 24V
POWER
SUPPLY
T7047C 
t
T1
T2
T
T
M3386
W960 OR
W927 PANEL
T7047C 
t
M3418
T
T
Q7300
T
T
T7047C
T
T
T7047C
T
T
T7047G1000
M10019
A1
A1
EXCEL 500/100/80
CONTROLLER
T7047H
COMMON